7. Turn on the Analyzer.
8. The Analyzer's firmware version displays, followed by battery status.
Output Analyzer
Version 1.1
9. SELECT TOOL USE displays next. Press and release the SELECT button until EPC TOOL displays. Press ENTER to
select this option. The device will prompt you to connect the leads.
Fike Analyzer
Select Tool Use
10. Press and release the ENTER button to initiate the test. The following screen will display:
EPC Analyzer
Leads Connected
11. As soon as the Analyzer tool recognizes there is an active connection, it will start its countdown:
Wait: Charging
Countdown: 30
12. Once the countdown timer completes, the display will indicate the system is ready for activation.
System Ready
Activate Now
13. Press and release the ACTIVATE button on the Analyzer to initiate the test.
14. The Analyzer will initiate the EPC series firing circuit and display the activation current readings obtained during
the test. EPC PASSES / REPLACE EPC will display on the front panel of the Analyzer. (See Section 7.2, Interpreting
EPC Measured Results, for more information or if you have questions regarding the results.)
5.97 5.7 5.5 5.2
EPC Passes
15. Record the readings obtained for future reference, since subsequent tests will override current test data.
16. Replace the minimum resistance shunt on the Analyzer with the 10-ohm resistor. Reset the EPC and make sure
it is in "normal" status, with no trouble light on.
17. Repeat Steps 7-14 and record the test readings obtained for future reference.
18. Press and release the SELECT and ENTER buttons at the same time to return to the Main Menu.
19. Select the EPC TOOL option from the Main Menu to prepare for the next test.
Doc. P/N 06-905
Rev. 1 / December 2018
VBat: 4.03
Battery at 100%
EPC Analyzer
Connect Leads
2.8 2.7 2.7 2.6
REPLACE EPC