Safety Instructions; Technical Data - Eaton CROUSE-HINDS Series Operating Instructions Manual

Explosion protected emergency light fittings
Hide thumbs Also See for CROUSE-HINDS Series:
Table of Contents

Advertisement

1.

Safety instructions

For skilled electricians and
trained personnel in accordance
with national legislation,
including the relevant standards and,
where applicable, in acc. with
IEC/EN 60079-14 on electrical apparatus
for explosive atmospheres.
– The light fitting must not be operated in
zone 0 or zone 20 hazardous areas!
– The light fitting must not be use while
excessive deposit of dust
(accd. IEC/EN 60079-31) exist.
– The technical data indicated on the light
fitting are to be observed!
– Changes of the design and modifica-
tions to the light fitting are not
permitted!
– The light fitting shall be operated as
intended and only in an undamaged and
perfect condition!
– Only genuine Cooper Crouse-Hinds
(CCH) / CEAG spare parts may be used
for replacement!
– Repairs that affect the explosion
protection, may only be carried out by
CCH/CEAG or a qualified "electrician"!
– These operating instructions shall not
be kept inside the light fitting during
operation!
The national safety rules and regulations
for prevention of accidents and the
following safety instructions which are
marked with an ( ) in these operating
instructions shall be observed!
10
Explosion protected emergency light fittings
Series: eLLK(M)(S)92 LED 400(800) NE
2.

Technical data

Type examination certificate:
Marking acc. to 2014/34/EU and standard:
EN 60079-0
gas
dust
IECEx type examination certificate:
Category of application
IEC 60079-0
gas
dust
Rated voltage AC ± 10 %
Rated frequency range:
cos p
Version
Rated current
120 V AC/DC
230 V AC/DC
254 V AC/DC
Rated power
LED 400
LED 800
Emergency operation time
Luminous flux factor (emerg. light)
related to 1 LED row in rated
operation:
Immunity from interference to IEC/EN 61000-6-2: fulfilled
Emission of interferences to EN 61000-6-4:
Insulation class to IEC/EN 61140
Degree of protection IEC/EN 60529
(1)
Perm. ambient temperature
eLL. 92 ..LED NE
apecitied
Storage temperature in original packing
Supply terminal clamping capacity
2 x per terminal
min.
max.
Conductor cross-section with through-wiring
Ex-e cable entry
Standard version
suitable cables and test torques of the pressure
srew
1 2
3
Seal 1+2+3
Seal 1+2
1 2
Seal 1
1 2
Metal
Test torque for screw in thread cable entry:
Test torque for breathing plug M25 x 1,5:
(1)
Intensive sun radiation in areas of high ambient temperatures may cause inadmissible temperature rise inside
of the luminaire. This may result a decrease in lifetime of the electronic ballast (EVG). Therefore those
luminaires should be switched off during daytime by a photocell control.
(2)
The tests of clamping ranges and torque values were performed with metal mandrel. The clamping range can
vary by using cables with different manufacturing tolerances and material properties. Please use the
combination of sealing 1 + 2 + 3 for the intermediate region.
(3)
When selecting the seal rubber, ensure that the cap nut can be tightened when carrying out any future
maintenance work on the cable entry.
BVS 09 ATEX E 034
II 2 G Ex d e mb ib IIC T4 Gb
II 2 D Ex tb IIIC T80 °C Db
IEC Ex BVS 09.0033
Ex d e mb ib IIC T4 Gb
Ex tb IIIC T80 °C Db
120 V to 254 V
50 to 60 Hz
> 0,95
LED 400
0,40
0,20
0,18
45 VA
70 VA
1.5 h
3.0 h (see wiring diagram)
LED 400
at 1.5 h
ca. 95 %
at 3.0 h
ca. 65 %
fulfilled
I
IP66
-25 °C to +45 °C
-5 °C to +35 °C
-25 °C to +45 °C
single-wire
1.5 mm²
6.0 mm²
2.5 mm² for max. 16 A
M25 x 1.5
Ø
min.
8.0
(2)(3)
max.
10.0
min.
10.0
3
(2)(3)
max.
13.0
min.
13.5
3
(3)
max.
17 .5
M20 x 1.5 thread
3,0 Nm
3,0 Nm
GB
LED 800
0,60
0,35
0,30
LED 800
ca. 65 %
ca. 45 %
multi-wire
1.5 mm²
6.0 mm²
Nm
1.5
2.0
2.3
2.6
1.3
2.3