Summary of Contents for National Instruments FieldPoint cFP-DI-304
Page 1
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...
Page 2
™ FieldPoint Operating Instructions cFP-DI-304 32-Channel, 24 VDC Sinking Digital Input Module These operating instructions describe how to install and use the cFP-DI-304 digital input module. For information about configuring and accessing the cFP-DI-304 over a network, refer to the user manual for the FieldPoint network module you are using. Features The cFP-DI-304 is a FieldPoint digital input module with the following features:...
Page 3
3. Using a number 2 Phillips screwdriver with a shank of at least 64 mm (2.5 in.) length, tighten the captive screws to 1.1 N ⋅ m (10 lb ⋅ in.) of torque. The nylon coating on the screws prevents them from loosening.
Page 5
Table 1. Terminal Assignments (Continued) Terminal Channel You can wire each channel for use with a sourcing-output device. A sourcing-output device provides a path to a voltage source. cFP-DI-304 ni.com Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com...
Status Indicators The cFP-DI-304 has two green status LEDs, POWER and READY. After you insert the cFP-DI-304 into a backplane and apply power to the connected network module, the green POWER indicator lights and the cFP-DI-304 informs the network module of its presence.
• For Compact FieldPoint, you must connect the protective earth (PE) ground terminal on the cFP-BP-x backplane to the system safety ground. The backplane PE ground terminal has the following symbol stamped beside it: . Connect the backplane PE ground terminal to the system safety ground using 14 AWG (1.6 mm) wire with a ring lug.
Specifications These specifications are typical for the range –40 to 70 °C unless otherwise noted. Specifications are subject to change in future revisions. Input Characteristics Number of channels......32 Input voltage ........0–30 VDC Input type .......... Sinking Digital logic levels OFF state Input voltage ......
Safety Standards This product is designed to meet the requirements of the following standards of safety for electrical equipment for measurement, control, and laboratory use: • EN 61010-1, IEC 61010-1 • UL 61010-1 • CAN/CSA-22.2 No. 61010-1 Note For UL and other safety certifications, refer to the product label, or visit , search ni.com/certification...
National Instruments corporate headquarters is located at 11500 North Mopac Expressway, Austin, Texas, 78759-3504. National Instruments also has offices located around the world to help address your support needs. For telephone support in the United States, create your service request at ni.com/support...
Page 15
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other product and company names mentioned herein are trademarks or trade names of their respective companies.
Page 16
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment SERVICE CENTER REPAIRS WE BUY USED EQUIPMENT • FAST SHIPPING AND DELIVERY Experienced engineers and technicians on staff Sell your excess, underutilized, and idle used equipment at our full-service, in-house repair center We also offer credit for buy-backs and trade-ins •...