7. Exit Configuration: Press the ESC key twice to exit the menu.
8. Choose Menu 2 Setpoints.
2 Setpoints
SETPOINTS POS: XXX
High Temp. X°C
High temperature setpoint
Low Temp. X°C
Low temperature setpoint
Delay: 2m
High or low temperature delay
Priority: --
High or low temperature alarm priority
Setpoint x°C
Temperature setpoint (only sensor Rx.1 .. Rx5)
Hystersis XK
Hysteresis setpoint (only sensor Rx.1 .. Rx5)
Name:Temp. Rx.y XK
Name of sensor (can only be edited on System Centre / Store Computer)
Pos.: Pos.1
Sensor Item IF
Offset 0K
Temperature sensor offset
Def. End. Tmp. x°C
Defrost termination temperature setpoint (only shown for sensors Rx.1 .. Rx.5)
EU Arch. CAN XX
CAN bus address of case/coldroom controller for which temperature is to be recorded.
No recording takes place when set to "-".
EU Arch. Zone XX
Temperature zone of case/coldroom controller for which temperature is to be recorded:
1 to 2 Temperature zone of case/coldroom controller
3 to 10 Temperature sensor (e.g. another UA 410 L in the system)
9. Changing the basic configuration of the controller
Return to the main menu by repeatedly pressing the ESC key.
The basic configuration of the controller is now completed.