Cisco NCS 2002 Installing page 10

Installing the air flow regulator
Hide thumbs Also See for NCS 2002:
Table of Contents

Advertisement

DLP-L69 Installing Air Plenum in NCS 2002 Shelf for ANSI 23-inch Configuration
Figure 10: Installing the horizontal air plenum in the ANSI 23-inch configuration
Step 5
Install the vertical air plenum to the left of the horizontal air plenum:
a) Insert the vertical air plenum in the free space between the horizontal air plenum and cabinet.
b) Install the wing head screws from the internal side of the horizontal plenum as shown in the following
figure.
c) Tighten the screws to a torque value of 11.5 in-lb (1.3 N-m).
Figure 11: Installing the left vertical air plenum
Step 6
Install the vertical plenum to the right of the horizontal air plenum. Follow step 5a to 5c.
Installing the Air Flow Regulator
10
Installing the Air Flow Regulator