Carrier AGATWNPME01B Installation Instructions Manual page 10

Twinning kit, for single-stage and two-stage, variable speed condensing and non-condensing gas furnaces
Table of Contents

Advertisement

AGATWNPME01B: Installation Instructions
A10277
Fig. 13 – Platform Installation of Stacked Non-Condensing Furnaces
1/4"
ROLLOUT PROTECTION REQUIRED
Install 12" x 22" (204 x 559 mm) sheet metal
above the burner compartment area. Sheet
metal MUST extend above the furnace casing
by 1" (25 mm) with door removed. A 1" (25 mm)
clearance minimum between top of furnace
and combustible material is required. Entire
length of furnace must be supported with
furnace is used in horizontal position to ensure
proper drainage.
1/4"
L14F014A
Fig. 14 – Suspended Installation of a Condensing Furnace
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents