Modbus Map - Emerson Copeland CoreSense 571-0065-05 Bulletin

Communications for 20 to 40 ton copeland scroll air conditioning compressors
Table of Contents

Advertisement

Note: Number of registers value to be send in the query = Number in the column "Message Length With Zero Stuffing" / 2
(e.g. number of reg required to read "Seven day Warning history with cumulative count" is 36 (72/2)
Read Only Data
Read Write Data
Write Only Data
Location
Parameter
in Hex
CoreSense Module Firmware
300
Version
308
CoreSense Module Model Number
314
ASSET Serial Number
320
ASSET Model Number
332
CoreSense Module Serial Number
33D
Division Name
35A
Product Code
363
Product Name
36A
Product type
36B
Endian Convention
36C
Dip switch Setting
380
Alarm Code
© 2016 Emerson Climate Technologies, Inc.
Table 4 – CoreSense Modbus Map
Parameters can be read using Function code 4 (Read Input Register)
Message
Length
in Bytes
8
12
12
18
11
29
9
7
1
1
2
1
Message
Length
With Zero
Stuffing
16
24
24
36
22
58
18
14
2
2
2
Unused (18 bytes)
0 - Normal Operation
1 - Loss of Communication to E2
2 - Open OR Short Spare Thermister Warning
3 - Open OR Shrt Scroll Thermister Warning
4 - Short Cycle Warning
5 - Module Low Voltage Trip
6 - Spare High Temperature Trip
7 - Missing Phase Trip
8 - Scroll High Temperature Trip
2
9 - Motor Thermister Open OR Short Trip
10 - Motor High Temperature Trip
11 -Short Cycle Lockout
12 - Spare High Temperature Lockout
13 - Motor High Temperature Open OR Short Lockout
14 - Reverse Phase Lockout
15 - Missing Phase Lockout
16 - Scroll High Temperature Lockout
17 - Motor High Temperature Trip Lockout
18 - P47 Module Failure
10
AE8-1384 R5