Led Flash Code Information - Emerson Copeland CoreSense 571-0065-05 Bulletin

Communications for 20 to 40 ton copeland scroll air conditioning compressors
Table of Contents

Advertisement

Parameters can be write using Function code 16 (Preset Multiple Registers)
Location
Parameter
in Hex
100
Customer Id Code
104
Customer Location
115
Customer Name
126
Compressor Model Number Modified
138
Compressor serial number
144
Application code
147
Temperature code
14B
Refrigerant code
152
Functional Configuration
Compressor run time to count as short
154
cycle
155
Scroll High Temp Trip
157
Scroll High Temp Reset
159
No. of Events to Phase Loss Lockout
15A
Future Use
15B
Future Use
15D
Future Use
No.of Events to Scroll High Temp
15F
Lockout
160
No.of Events to Short Cycling Warning
16A
Write Command
© 2016 Emerson Climate Technologies, Inc.
Table 4 – CoreSense Modbus Map Continued
Message
Length in
Bytes
13
Message
Length
With Zero
Stuffing
4
8
17
34
17
34
18
36
12
24
3
6
4
8
7
14
2
2
1
2
Range: 1 min to 6 min
2
2
Range: 110 deg C to 150 deg C
Note: Reset set point value should
2
2
be always (Trip set point value -
30 deg C)
1
2
Range: 4 to 24
1
2
Range: 4 to 36
1
2
Range: 20 to 200
Options: 0x0800(Alarm Reset) &
2
2
0x8000(Module Reset)
AE8-1384 R5