How To Use The Vent Graph; Rear Wall Vent Application & Installation - Majestic fireplaces DV580, DV360 Installation And Operating Manual

Direct vent gas fireplace
Hide thumbs Also See for DV580, DV360:
Table of Contents

Advertisement

DV360/580 Series Direct Vent Gas Fireplace
Twist Lock Pipes
When using twist lock pipe it is not necessary to use
sealant on the joints. The only areas of the venting
system that need to be sealed with high temperature
silicone sealant are the sliding joints of any telescopic
vent section used in the system.
To join twist lock pipes together, simply align the beads
of the male end with the grooves of the female end,
twisting the pipe until the flange on the female end
contacts external flange on the male end. It is recom-
mended that you secure the joints with three (3) sheet
metal screws, however, this is not mandatory with twist
lock pipe. (Fig. 18)
To make it easier to assembly the joints, we suggest
putting a lubricant (Vaseline or similar) on the male end
of the twist lock pipe prior to assembly.
Male End
Screw Holes
Fig. 18 Twist-lock pipe joints.

How to Use the Vent Graph

TWL100
The Vent Graph should be read in conjunction with the
Twist Lock Pipe
following vent installation instructions to determine the
3/12/99 djt
relationship between the vertical and horizontal dimen-
sions fo the vent system.
1. Determine the height of the center of the horizontal
vent pipe exiting through the outer wall. Using this
dimension on the Sidewall Vent Graph (Fig. 19),
locate the point intersecting with the slanted graph
line.
2. From the point of this intersection, draw a vertical
line to the bottom of the graph.
3. Select the indicated dimension, and position the
fireplace in accordance with same.
EXAMPLE A:
If the vertical dimension from the floor of the unit is 11'
(3.4m) the horizontal run to the face of the outer wall
must not exceed 14' (4.3m).
EXAMPLE B:
If the vertical dimension from the floor of the unit is 7'
(2.1m), the horizontal run to the face of the outer wall
must not exceed 8¹⁄₂' (2.6m).
14
Female End
TWL100
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
3
4
5 6 7
Horizontal dimension from the outside face of the
wall to the center of the fireplace vent flange
Fig. 19 Sidewall venting graph. (Dimensions in feet)
Refer to Page 20 for venting requirements for snor-
kels.
Rear Wall Vent Application
When installed as a rear vent unit this appliance may be
vented directly to a termination located on the rear wall
behind the appliance.
• Only CFM Corporation venting components are
approved to be used in these applications (See
'Venting Components' listed for different installation
requirements).
• The maximum horizontal distance between the rear
of the appliance (or end of the transition elbow in a
corner application) and the outside face of the rear
wall is 20" (508mm). (Fig. 20, 21)
• Only one 45° elbow is allowed in these installations.
• Minimum clearances between vent pipe and com-
bustible materials are as follows:
Top - 2" (51 mm)
Sides - 1" (25 mm)
Bottom - 1" (25 mm)
eg: A
eg: B
8 9 10 11 12 13 14 15 16 17 18 19 20
20010667

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents