Vertical Through The Roof Applications - Vermont Castings D232 Installation Instructions & Homeowner's Manual

Free-standing direct vented fireplaces
Table of Contents

Advertisement

Ensure sidewall venting clearances are observed.
If installing a snorkel a minimum 24" vertical rise is
necessary. The maximum horizontal run with the 24"
vertical pipe is 36" (915mm). This measurement is
taken from the collar of the fireplace to the face of the
exterior wall. See vent graph for extended horizontal
run if the vertical exceeds 24".
1. Establish vent hole through the wall (Fig. 13,14 & 15).
2. Remove soil to a depth of approximately 16" below
base of snorkel. Install drain pipe. Install window well
(not supplied). Refill hole with 12" of coarse gravel
leaving a clearance of approximately 4" below snorkel.
See Fig. 22.
3. Install vent system.
4. Ensure a watertight seal is made around the vent pipe
coming through the wall.
5. Apply high temperature sealant caulking (supplied)
around the 4 and 7 inch snorkel collars.
6. Slide into vent pipe and secure to the wall.
7. Level the soil so as to maintain a 4" clearance below
snorkel. See Fig. 22.
FIRESTOP
7" PIPE
24"/608mm
MINIMUM*
SNORKEL
SCREWS
4" CLEARANCE
GROUND
WINDOW WELL
GRAVEL
DRAIN
FOUNDATION WALL
*
A minimum of 24"/608mm
vertical pipe must be installed
when using the snorkel kit.
*
The 22" vertical rise (center to
center) of the snorkel may be
included for calculation of max.
horizontal run.
Fig. 22
DO NOT BACK FILL AROUND SNORKEL.
SOIL SHOULD NOT BE LESS THAN 4"
BELOW SNORKEL.
FOUNDATION
RECESS
WATERTIGHT
SEAL
AROUND
PIPE
If the foundation is recessed, use recess brackets (not
supplied) for securing lower portion of the snorkel. Fasten
brackets to wall first and then secure to snorkel with self drilling
#8 x 1/2 sheet metal screws. It will be necessary to extend the
vent pipes out as far as the protruding wall face (Fig. 22).
VERTICAL THROUGH THE ROOF
MINIMUM
8 FT./
MAXIMUM
40 FT.
VERTICAL
RISE
This Gas Fireplace has been approved for,
a) Vertical installations up to 40 feet (12 metres) in height.
Up to a 10 ft. horizontal vent run can be installed within
the vent system using a maximum of two 90
(Fig. 24)
o
b) Up to two 45
elbows may be used within the horizontal
run. For each 45
the maximum horizontal length must be reduced by 18
inches.
Example: Maximum horizontal length
0
1
2
- 14 -
SNORKEL
WALL
SCREWS
SHEET METAL
SCREWS
APPLICATIONS
MAXIMUM
10 FT
(305cm)
PIPE STRAPS
EVERY 3'
(92cm)
o
elbow used on the horizontal level
-
45
o
elbows
10 ft.
o
-
45
elbows
8.5 ft.
o
-
45
elbows
7 ft.
Fig. 23
Fig. 24
o
elbows.