Product Documentation of the LSN Radio Fire Detection System
⇒ Following a successful system logon (duration:
15 seconds to a max. of 10 minutes), the LED will
go out and then flashes again for two minutes to
indicate the field strength.
Flashes/sec.
4
3
2
1
⇒ The yellow LED lights up briefly to acknowledge
each successful logon.
D All RF detectors (maximum of 30) are logged on to
FK 100 LSN in this way one after the other.
D Wait until the LED (flashing to indicate field
strength) on the last detector goes out.
D Activate the RF expansion module by moving the
magnets along the left - hand side of FK 100 LSN
housing.
⇒ The green LED flashes slowly, indicating that
FK 100 LSN has started system configuration.
⇒ Following successful system configuration, the
green LED lights up permanently, indicating that
the radio cell is in standard mode.
Avoid disconnecting the expander power supply after initial set- up
of the radio cell, as all detectors search for their RF expansion mod-
ules during power off condition and are therefore constantly trans-
mitting, which substantially reduces the service life of the batteries.
If it is necessary to disconnect the power supply for a long period
(> 1 hour), remove the batteries from the RF detectors.
Field strength
High
Moderate
Low
Very low
Seite 22 von 32
LED
red
Effect
Within field strength range adequate for
Within field strength range adequate for
detector use!
Impermissible field strength range!
Impermissible field strength range!
Improve detector positioning!
LED
LED
PI - 32.15a
Reed switch
yellow
green
601-F.01U.002.708
A3.en / 28.12.2004
ST-FIR/ PRM1 / deh