Fujitsu AS G07LUCA Series Service Instruction page 77

Universal floor/celling slim duct/mini duct compact cassette compact wall mounted/floor wall mounted type, inverter multi, refrigerant r410a, indoor/outdoor unit
Hide thumbs Also See for AS G07LUCA Series:
Table of Contents

Advertisement

Trouble shooting 17
INDOOR UNIT Error Method:
Damper(OPEN/CLOSE) Simultaneous
Detection Limit Switch Error
Detective Actuators:
Indoor unit Controller PCB Circuit
Limit switch
Forecast of Cause :
1. Limit switch failure
Check Point 1 : Check Limit switch
Check operation of limit switch. (any blocking by dust, etc.)
Remove Limit switch and check ON/OFF switching operation by using a meter.
>>If Limit switch is detective, replace it.
OK
OK
Check Point 2 :
Check Point 2 : Check Connector (CN18) / Wire
Check loose contact of CN18 /shorted wire (pinched wire).
>>Replace Limit switch if the wire is abnormal
OK
OK
Check Point 3 : Replace Controller PCB
If Check Point 1 & 2 do not improve the symptom, change Controller PCB.
Indicate or Display:
Indoor Unit
Operation lamp : 5 time Flash
Timer lamp          : 7 time Flash
ERROR CODE : [E : 57]
Detective details:
When the limit switch detects open and close at the simultaneous.
2. Shorted connector/ wire
02-32
Outdoor Unit
A
B
5
15
: Light ON
: Light OFF
3. Controller PCB failure
Monitor
C
D
E
F
n : n time blinking