3.2.3 Setting the Module Switches
The functions of the module user switches are shown below:
Switch
Use
Position
1
Remote Firmware Update
2
SD Card Firmware Update
3
Clear Exception Pushbutton
4
SD Card Ethernet Port Setup
5
Remote Controller Reset
6 - 12
Reserved
See the illustration in the preceding
CTI Janus Programmable Automation Controller IOG
Open Position
Disabled
Normal
operation
Disabled
Disabled
Disabled
Section 3.2.2
for the location of the switches.
Closed Position
Enables firmware update via web
server. See
Section 6.3
for details.
Controller enters Front Panel SD Card
Firmware Update mode at startup.
See
Section 6.2
for details.
Enables the recessed pushbutton to be
used to clear exceptions, configuration
reset, or to restore factory settings.
See
Section
5.3.
Allows user to configure controller
Ethernet Port A via front panel SD card.
NOTE: This setting works ONLY if Switch
2 is OPEN. See
Section
3.2.9.
Enables the ability to clear exceptions,
Configuration Reset, and Restore
Factory Settings using the embedded
web server.