Download Print this page
Lutron Electronics Maestro MRF2S-8SD010 Manual

Lutron Electronics Maestro MRF2S-8SD010 Manual

Vive sensor dimmer/switch

Advertisement

Available languages

Available languages

Quick Links

Vive Sensor Dimmer / Switch
Part of the Vive System
032538
Please read before installing
Rev. A
05/2019
Maestro 0–10 V- RF Sensor Dimmer
MRF2S-8SD010
Occupancy / Vacancy
MRF2S-8SDV010
Vacancy Only
Maestro RF Sensor Switch
MRF2S-8SS
Occupancy / Vacancy
MRF2S-8SSV
Vacancy Only
For set-up, programming, and troubleshooting
with a Vive system, please refer to the installation
instructions included with the Vive hub or at
www.lutron.com/vive
Lighting
Sensor Dimmer
0-10 V- electronic fluorescent ballast or LED driver
Sensor Switch
All lighting loads and up to 4.4 A fan loads
120/277 V~ 50/60 Hz 8 A
Canada: 120 V~ 50/60 Hz 8 A
Compatible Devices for Sensor Dimmer
• Works with all ballasts and drivers that provide a current source
compliant to IEC 60929 Annex E.2.
• Supports Electronic Off functionality for voltages less than 0.5 V
0–10 V- Load Rating (sink only)
• One sensor dimmer can sink up to 50 mA of current.
• Controls up to 25 drivers or ballasts.
• IEC 60929 Annex E.2 requires each driver / ballast to limit the current
draw to 2.0 mA maximum.
Motion Coverage
• Major: 30 ft × 30 ft (9 m × 9 m) [900 ft
2
(81 m
2
)]
• Minor: 20 ft × 20 ft (6 m × 6 m) [400 ft
2
(36 m
2
)]
Wireless Communication
• Range of wireless communication is 60 ft (18 m) line-of-sight or 30 ft
(9 m) through walls.
• Keep all wireless devices visible within the space. Do not place behind
large furniture or appliances.
Important Notes:
• Neutral is required for product to function. If a neutral wire is not present,
consult a licensed electrician.
• When controlling light and fan loads simultaneously on a single switch,
the maximum load capacity per switch is 4.4 A at 120 V~. Only the
sensor switch can be used to control fan loads.
• When power is applied, the sensor dimmer / switch can be manually
turned On / Off after the first 10 seconds and the sensor will
automatically control the load after 2 minutes.
• The sensor requires an unobstructed view of the room and line-of-sight
to detect motion.
• Hot objects or moving air currents can affect the performance of the
sensor and may cause it to turn on unexpectedly or not function as
desired.
• CAUTION: To reduce the risk of overheating and possible damage to
other equipment, DO NOT use to control receptacles.
• Class 2 / Class 1 wiring: Install in accordance with all national and local
electrical codes.
• For indoor use only. Operate between 32 °F – 104 °F (0 °C – 40 °C),
ambient. 0% to 90% humidity, non-condensing.
• Clean only with soft, damp cloth, DO NOT use chemical cleaners.
Lutron Electronics Co., Inc. 7200 Suter Road
Coopersburg, PA 18036-1299 USA
Start Here
Wiring
For more information and additional wiring instructions, visit: www.lutron.com/TechnicalDocumentLibrary/048687.pdf and / or
www.lutron.com/TechnicalDocumentLibrary/3691097.pdf
Note: The two black wires are interchangeable; either one can be wired to hot or switched hot.
1. Turn off power at the circuit breaker or fuse.
WARNING: Electric Shock Hazard. May result in Serious Injury or Death.
Turn OFF power at circuit breaker or fuse before installing or servicing the unit.
Up to 25 drivers total and
2. Connect Wires.
up to 50 mA maximum
a. Sensor Dimmer - Single Pole Wiring
Line / Hot
lutron.com
1.844.588.7661
Black
Turn Off Power
Black
Arrêtez le Courant
Desconecte la
Corriente
120/277 V~ 50/60 Hz 8 A
Gray (–)
120 V~ 50/60 Hz 8 A Canada
Violet (+)
Green
White
Ground
Neutral
b. Sensor Switch - Single Pole Wiring
Line / Hot
lutron.com
Black
Black
1.844.588.7661
Turn Off Power
Arrêtez le Courant
Desconecte la
Corriente
120/277 V~ 50/60 Hz 8 A
120 V~ 50/60 Hz 8 A Canada
120 V~ 50/60 Hz 4.4 A Fan Loads
Green
White
Ground
Neutral
c. For instructions on how to install these devices in a multi-location retrofit application such as 3-way installation, please refer to the
app note located at www.lutron.com/TechnicalDocumentLibrary/048687.pdf
3. Install device into the wallbox. Do not install wallplate at this time.
4. Turn on power at circuit breaker or fuse.
WARNING: Electric Shock Hazard. Could result in minor or moderate personal injury.
Ground connection required before connecting power.
5. Wait two minutes.
• The sensor dimmer / switch will manually control the load after the first 10 seconds.
• Once power has been restored, the sensor dimmer / switch will automatically control the load after the first two minutes.
6. Program all desired settings before installing the wallplate.
• See other side of sheet for details on how to program settings.
FCC Supplier Declaration to Conformity / IC Information
This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not
cause interference and (2) This device must accept any interference, including interference that may cause undesired operation. Modification not expressly approved by Lutron Electronics
Co., Inc. could void the user's authority to operate this equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
• Re-orient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
Customer Assistance | 1.844.LUTRON1 U.S.A. / Canada | +1.888.235.2910 Mexico | +1.610.282.3800 Others | www.lutron.com/support
Programming with a Vive Hub
1. Use an iOS
compatible device.
Turn OFF power
Up to 25 drivers total
and up to 8 A maximum
Gray (–)
White
Ballast or
Violet (+)
Black
Driver
Gray (–)
White
Ballast or
Violet (+)
Black
Note: For further information on set up, programming, and troubleshooting with a Vive system, please refer to the
Driver
installation instructions included with the Vive hub or visit www.lutron.com/vive
Associating wireless devices to a sensor dimmer / switch
1. Press and hold
and the load lights flash (about
7 seconds), then release. Note that
after about 3 seconds the PIR lens
will light up, but keep holding
the other lights flash.
White
Ballast or
Black
Driver
White
Ballast or
Black
Driver
Notes:
To associate multiple wireless devices, repeat steps 1 and 2 above for each wireless device.
To exit this mode without associating device press and hold
For instructions on how to use or set up the Pico wireless control, please see
http://www.lutron.com/TechnicalDocumentLibrary/040429.pdf
The device's internal ambient light detecting (ALD) sensor is disabled when associated to a remote daylight sensor.
Un-associating a wireless device from a sensor dimmer/switch
1. Triple-tap and hold the wireless device button
until the device lights begin to flash rapidly.
Within 1 second of flashing, release and triple-
Turn ON power
tap the button again. The button does not need
to be held after the second triple-tap.
Note: This will un-associate the wireless device from all devices, not just the Sensor Dimmer / Switch.
2. Download the Lutron Vive app.
or Android
®
®
X
until the
lights
2. Press and hold the wireless device button shown below until the lights
T
ML
stop flashing (about 6 seconds).
Pico wireless
Radio Powr Savr
control
daylight sensor
(up to 10)
(1 maximum)
until
T
Link
lutron.com
Test
1.844.588.7661
Turn Off Power
T
Arrêtez le Courant
Desconecte la
ML
Corriente
T
until the lights stop flashing (about 7 seconds).
2. To test that the wireless device has been successfully
un-associated, press "Test" or
wireless device no longer controls the load.
Link
Test
3. Open the app and follow
the instructions.
Vive
X
Radio Powr Savr
occupancy / vacancy sensor
(up to 10)
d
and verify that the
Link
Test

Advertisement

loading

Summary of Contents for Lutron Electronics Maestro MRF2S-8SD010

  • Page 1 This device complies with part 15 of the FCC Rules and Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) This device may not cause interference and (2) This device must accept any interference, including interference that may cause undesired operation. Modification not expressly approved by Lutron Electronics ambient.
  • Page 2: Reset Factory Default Settings

    Fixd Lutron Electronics Co., Inc. 7200 Suter Road Lutron, Radio Powr Savr, Pico, Maestro, and Vive are trademarks or registered trademarks of Lutron Electronics Co., Inc. in the U.S. and other countries. Coopersburg, PA 18036-1299 USA App Store is a service mark of Apple, Inc. Android and Google Play are registered trademarks of Google LLC. iOS is a trademark or registered trademark of Cisco in the U.S. and other countries and is used under license.
  • Page 3 (1) Cet appareil ne doit pas provoquer d’interférences et (2) Cet appareil ne doit accepter aucune interférence, y compris des interférences qui pourraient provoquer un fonctionnement indésirable. Les modifications qui n’ont pas été expressément approuvées par Lutron Electronics Co., Inc. peuvent annuler le pouvoir de l’utilisateur d’utiliser cet avec les codes électriques en vigueur.
  • Page 4: Mode Test

    Fixd Lutron Electronics Co., Inc. 7200 Suter Road, Lutron, Radio Powr Savr, Pico, Maestro et Vive sont des marques commerciales ou des marques déposées de Lutron Electronics Co., Inc., aux États-Unis et dans d’autres pays. Coopersburg, PA 18036-1299, États-Unis App Store est une marque de service de Apple Inc. Android et Google Play sont des marques déposées de Google LLC. iOS est une marque commerciale ou une marque déposée de Cisco aux États-Unis et dans d’autres pays, utilisée sous licence.
  • Page 5 (1) Este dispositivo no debe causar interferencias y (2) este dispositivo debe aceptar cualquier interferencia, incluida la interferencia que pudiera ocasionar una operación no deseada. Las • Cableado Clase 2 / Clase 1: Instale de acuerdo con todas las modificaciones no aprobadas expresamente por Lutron Electronics Co., Inc. podrían invalidar la autorización del usuario para utilizar este equipo. normativas eléctricas nacionales y locales.
  • Page 6: Solución De Problemas

    Fixd Lutron Electronics Co., Inc. 7200 Suter Road Lutron, Radio Powr Savr, Pico, Maestro y Vive son marcas comerciales o marcas comerciales registradas de Lutron Electronics Co., Inc. en E.U.A. y otros países. Coopersburg, PA 18036-1299, E.U.A. App Store es una marca de servicio de Apple Inc. Android y Google Play son marcas comerciales registradas de Google LLC. iOS es una marca comercial o una marca comercial registrada de Cisco en E.U.A. y en otros países y se utiliza bajo licencia.

This manual is also suitable for:

Maestro mrf2s-8sdv010Maestro mrf2s-8ssMaestro mrf2s-8ssv