Operating Instructions
1.
Safety Information
The housing of the meter shall not be opened.
Changes in the data telegram or the transmission rate
affect your battery life.
The meter sends no data telegram after delivery ex
factory. The transmission starts after the installation of
the meter.
2.
Description of function
The wireless M-Bus function enables the meter to communi-
cate with a stationary (radio concentrator) or mobile unit
(handheld, smartphone) using 868 MHz radio frequency (unli-
censed). The function supports the OMS-compliant data trans-
fer.
The wireless M-Bus function is available in 2 versions:
with in the meter integrated antenna
with external antenna
3.
OMS-compatible data output
The meter sends data telegrams acc. to the "open metering
system specification volume 2 primary communication issue
3.0.1 / 2011-01-29".
Note: The wireless M-Bus function supports only the T1
mode acc. to the EN 13757-4. Therefore, receiving data
telegrams, such as time synchronisation, is not possible.
The following data is available by default for the stationary data
reading (data telegram F000):
Current energy
Current volume
Current flowrate
Current power
Current flow and return temperature
Error (manufacturer specific)
Current timestamp (type I)
The following data are available by default for the mobile data
reading (data telegram F001):
Current energy
Current volume
Energy: previous month on reference date
Volume: previous month on reference date
Monthly reference date
Energy: previous year on reference date
Annual reference date
Error (manufacturer specific)
Current timestamp (type I)
More data telegrams can be parameterised at the factory or
later with the service software UltraAssist.
Warning: Changes in the data telegram or the trans-
mission rate affect your battery life.
Note: Detailed information for the parameterisation with
the service software can be found in the UltraAssist user
manual.
Siemens Building Technologies
Wireless M-Bus function WSM5.. / WSB5..
Wireless M-Bus function WSM6.. / WSB6..
4.
User loop "LOOP 0"
...
General/Communication "LOOP 3"
...
5.
After an accumulation of volume of at least 10 litres, the meter
starts the transmission automatically and starts with the regular
sending of the data telegram.
In addition, the following options are available to start the
transmission:
Starting the transmission in LOOP 0
Proceed as follows to start the transmission:
The transmission is activated and the LCD display will change
to
The meter starts with the regular sending of the data telegram
after about 1 minute.
A6V11285671_----_a
LCD-Display
Note: Both display range and data displayed can differ
from this description depending on the meter parameter-
isation. Certain button functions can also be blocked.
User loop
...
Send status "disconnect (Setbind)" or "con-
nect (bind)"
or
General/Communication
...
Type „RF" with „OMS"-protocol in 2 s cycles
with
send status „disconnect (unbind)" or „connect
(bind)"
or
Start-up
Starting the transmission in LOOP 0
Starting the transmission in "Para menu"
Note: The display value
per default on the side of the factory.
Hold the button several times long (for more than 3 s) until
appears on the LCD.
Press the button several times briefly (for less than 2 s)
until
appears on the LCD.
Press the button long (for more than 3 s).
.
A6V11285671_----_a
06.12.2017
Translation
is pre-parameterised
06.12.2017
3