2. Secure one end of the ground cable to the
ground bar inside the PDC, and secure the
other end to the ground grid or busbar of the
equipment room, as shown in the figure.
Ground positions are reserved on the left and
right sides at the upper part of the PDC.
Select one ground position based on the
position of the ground grid or busbar.
3. Connect input power cables. 4. Connect output power cables. 5. The following figure shows
6. Connect one end of the PDC monitoring cable to the
RS485_1 port on the LCD, and connect the other end to
northbound device port.
(1) Monitoring
cable outlet
In the micro-module scenario, the monitoring
cable is connected to the COM port of the
northbound ECC800.
13
the overall effect after
cable connection.