ABB Relion 615 Series List Manual page 36

Feeder protection and control
Hide thumbs Also See for Relion 615 Series:
Table of Contents

Advertisement

Section 3
Interoperability profile for 615 series IEC 60870-5-103
3.3.5
3.3.6
30
Basic application functions
⃞ Test mode
⃞ Blocking of monitor direction
⊠ Disturbance data
⃞ Generic services
⊠ Private data
Miscellaneous
Measurands are transmitted as Class2 data using ASDU 3 or ASDU 9. The default
MVAL scalings in 615 series devices is 2.4. User can freely reprogram the MVAL
for each separate measurand.
Measurand
Current L
1
Current L
2
Current L
3
Voltage L
1-E
Voltage L
2-E
Voltage L
3-E
Active power P
Reactive power Q
Frequency f
Voltage L
- L
1
2
The IED contains additional private Class2 frames, including private measurands.
User can freely select between standard or private Class2 frames.
Max. MVAL = rated value times
1.2 or
2.4
1MRS756712 C
REF615
Point List Manual