1 4 . B a t t e r y C h e c k s
Turn the battery circuit breaker to Off and disconnect all connectors in the battery set.
Record the requested information in the following table.
Battery manufacturer
CAUTION: RISK OF EXPLOSION IF A BATTERY IS REPLACED BY AN INCORRECT
TYPE.
DO NOT DISPOSE OF BATTERIES IN A FIRE. BATTERIES MAY EXPLODE.
DO NOT DISCARD BATTERIES IN THE TRASH. THIS PRODUCT CONTAINS SEALED
LEAD-ACID BATTERIES.
FOR PROPER DISPOSAL, CONTACT YOUR LOCAL RECYCLING OR HAZARDOUS
WASTE CENTER.
Use a power resistor of 0.5
across the terminals of each battery. The voltage measured across the resistor should be no less
than 10 Vdc for any battery. Replace any batteries that give a reading less than 10 Vdc.
BATTERY STRING #1
Batt.
Good
Bad
no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Centric Installation Guide, rel. 4.7
GAMATRONIC, A S
Battery model
Ω
(300 W rating recommended) for the load to check the voltage drop
Batt.
Good
Bad
no.
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
END OF MAINTENANCE PROCEDURES REPORT
E
D
OLAR
DGE
IVISION
Rating (Ah)
BATTERY STRING #2
Batt.
Good
no.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
Number of battery strings
(x 60)
Batt.
Bad
Good
no.
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Bad
77

Advertisement

Table of Contents
loading

This manual is also suitable for:

Centric 50 kwCentric 100 kwCentric 200 kw

Table of Contents