Endress+Hauser easytemp TSM 470 G Operating Instructions Manual
Endress+Hauser easytemp TSM 470 G Operating Instructions Manual

Endress+Hauser easytemp TSM 470 G Operating Instructions Manual

Compact rtd transmitter

Advertisement

easytemp
TSM 470 G /
BA 164R/24/ae/04.04
TSM 470 F / TSM 470 P
compact RTD transmitter
Operating instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the easytemp TSM 470 G and is the answer not in the manual?

Questions and answers

Summary of Contents for Endress+Hauser easytemp TSM 470 G

  • Page 1 ™ easytemp TSM 470 G / BA 164R/24/ae/04.04 TSM 470 F / TSM 470 P compact RTD transmitter Operating instructions...
  • Page 2 Preparing the communication with PC configuration software ⇓ Instrument configuration (including a description of the unit Page 11 functions) A complete description of all the functions as well as a detailed overview of the functionality can be found in this chapter. Endress+Hauser...
  • Page 3: Table Of Contents

    Compact RTD transmitter Endress+Hauser Table of contents Safety notes ....4 Designated use ......4 Installation, commissioning and operation .
  • Page 4: Safety Notes

    185 °F (-40 and 85 °C). Heat from the process is transferred from the thermowell to the transmitter housing. If the expected process temperature is near or beyond specification limits, consider the use of additional thermowell lagging, and extension nipple, or a remote mounting configuration to isolate the transmitter from the process. Endress+Hauser...
  • Page 5: Operational Safety

    – Devices that are used in hazardous areas or cables for such devices must have the corresponding type of protection. Safe area (non-hazardous areas)! This symbol identifies the non-hazardous area in the diagrams in these Operating Instructions. – Devices in non-hazardous areas must also be certified if connection cables run through a hazardous area. Endress+Hauser...
  • Page 6: Identification

    Authorization to continue to apply the 3-A Symbol to the models of equipment, conforming to 3-A Sanitary Standards for Sensors and Sensor Fittings and Connections Used on Fluid Milk and Milk Products, Number: 74-02 for TSM470P and TSM470F. American Bureau of Shipping (ABS) Ship Building Type Approval (TSM470G). Endress+Hauser...
  • Page 7: Delivery Contents

    • easytemp ™ ® and ReadWin 2000 are registered trademarks of Endress+Hauser Wetzer GmbH + Co. KG, Nesselwang, Germany Installation Installation conditions • When installing and operating the unit, please take note of the allowable ambient temperature (see chapter 10 "Technical Data").
  • Page 8: Installation

    The unit must only be powered by a power supply that operates using an IEC 61010-1 compliant energy limited circuit. " Caution! In order to avoid damaging the compact RTD transmitter, do not over-tighten the nut from on M12 micro-connector. Endress+Hauser...
  • Page 9: Wiring

    The best place to ground the loop is at the negative terminal of the power supply. Do not ground the current signal loop at more than one point. Endress+Hauser...
  • Page 10: Operation

    RS232C connector screws to the PC. If the PC does not have a RS232 serial interface, use a USB (UNIVERSAL SERIAL BUS) converter. Full compliance with the USB specifications Version 1.0.11.1 and USB CDC Version 1.1 are required to support the RS232 serial interface. Endress+Hauser...
  • Page 11: Commissioning

    • Install the configuration software and make connection to the PC (see Chap. 5, ’Operation’). • For detailed operating instructions for the PC configuration software please read the online documentation (BA137R/09/ae) contained in the PC operation and readout software (see folder ’Doc’). Endress+Hauser...
  • Page 12 Selection of the digital filter 1. order (filter time constant). Input: 0 to 8 s Offset Input of the zero point correction (offset). Input: -9.9 to 9.9 °C (-17.8 to 17.8 °F) 0.00 °C Measuring point Measuring point description ident Input: 8 characters Endress+Hauser...
  • Page 13: Maintenance

    (TTL/RS 232C) for configuration of the TSM470 G / TSM470 F / TSM470 P. TSM470A-VN Connector unshielded, female, angeled, M12 A coded, 4-pos. SONDTT-AG CD-ROM with all operation and instruction manuals, Endress+Hauser temperature measurement 52010285 5 m PVC connecting cable with M12x1 micro-connector Endress+Hauser...
  • Page 14: Trouble-Shooting

    Install sensor correctly Heat conducted by sensor Take note of sensor installation point Measured value incorrect/ Transmitter setup faulty (number of Change device function ’Connection inaccurate wires) mode’ Transmitter setup faulty (scale) Change scale Offset incorrectly set Check offset Endress+Hauser...
  • Page 15: Returns

    Software version / date Changes to software Changes to documentation 1.00.00 / 12.2002 Original firmware compatible with: • ® ReadWin 2000 1.10.1.0 and higher 1.01.00 / 06.2003 New oscillator frequency compatible with: • ® ReadWin 2000 1.13.0.0 and higher Endress+Hauser...
  • Page 16: Technical Data

    To NAMUR NE 43 high Source impedance max. (V - 10V) / 0.022 A (current output) power supply e. g. (24 V -10 V) / 0.022 A = 636.4 Ω Transmission behavior temperature linear ≤ 3.5 mA Min. current consumption Endress+Hauser...
  • Page 17 TSM470 G TSM470 F TSM 470 P Tube diameter 1/4" OD, 316L Tube diameter 3/8" OD reduced 3/16" OD, 316L Tube diameter 5/32" OD, 316L Reference operating Calibration temperature: 73.4 °F ± 9 °F (+23 °C ± 5 °C) conditions Endress+Hauser...
  • Page 18 ≤ ±0.01%/V deviation from 24 V Influence of power supply Percentages refer to the full scale value. ≤ 0.18 °F/year (≤ 0.1 °C/year) or ≤ 0.05%/year Long-term stability Values under reference operating conditions. % refer to the set span. The highest value is valid. Endress+Hauser...
  • Page 19 Burst (signal) IEC 61000-4-4 1 kV Transient voltage IEC 61000-4-5 1 kV unsym. / 0.5 kV sym. HF coupling IEC 61000-4-6 0.15 to 80 MHz 10 V Line interference IEC 61000-4-16 10 kHz to 150 kHz 10 V Condensation allowed Endress+Hauser...
  • Page 20 = flow velocity water or steam (Avoid resonance frequency as this will cause damage to the probe! Resonance frequency occurs when permanent flow velocity is at 31 ft/s (air) for the 5¼ " and / or 13 ft/s (air) for 8¼ " probe.) Endress+Hauser...
  • Page 21 Surface Finish TSM470 F & TSM470 P 32 micro-inches R and 20 micro-inches R are the two standard finishes provided for Milk service and Bioprocessing Equipment services respectively. The 32 micro-inch R maximum is defined in "3-A Sanitary Standards for Sensors and Sensor Fittings and Endress+Hauser...
  • Page 22 208 g 218 g TSM470F-_C2 218 g 245 g 272 g L in Inches (mm) ¾" (19.05) 1¼" (31.75) 2¾" (31.75) TSM470P 67 g 69 g 72 g Material Transmitter housing: stainless steel (SST). Wetted parts: SS 316L (1.4404). Endress+Hauser...
  • Page 23 Interface PC-interface connecting cable TTL -/- RS232 with plug-in connection. Configurable parameters Measuring dimension (°C/°F), measuring ranges, failure mode, output signal (4 to 20 / 20 to 4 mA), offset, filter (damping), set tag number (8 characters), output simulation. Endress+Hauser...
  • Page 24 10.0.12 Documentation Field of activities (FA) ’Temperature measurement’ (FA 006T/09/en) ™ Short form operating manual ’easytemp TSM 470’ (KA 148R/24/ae) ™ Technical information ’Compact RTD transmitter easytemp TSM 470 G / TSM 470 F / TSM 470 P’ (TI 101R/24/ae) Endress+Hauser...
  • Page 25: Index

    Compact RTD transmitter Endress+Hauser Index Numerics 3-A Sanitary Standard......6 American Bureau of Shipping (ABS) ... . . 6 Brief overview .
  • Page 26 Compact RTD transmitter Endress+Hauser Endress+Hauser...
  • Page 28 BA 164R/24/ae/04.04 FM+SGML6.0 ProMoDo...

This manual is also suitable for:

Easytemp tsm 470 fEasytemp tsm 470 p

Table of Contents