2 Installation
2.3
Installation space
Make sure to keep a minimum distance to other devices to avoid effects from noise or heat
and to permit unit replacement.
•
Leave at least 50mm of space between the wiring ducts of the unit and other devices to
allow heat radiation and unit replacement.
(1) 50mm or more
•
Maintain a minimum of 100mm between devices to avoid adverse affects from noise and
heat when installing a device or panel door to the front of the FP-I4C unit.
(1) 100mm or more
(2) Other device or panel door
•
Keep the first 100mm from the front surface of the FP-I4C unit open in order to allow
room for wiring.
2.4
Attach the unit to a DIN rail
The FP-I4C unit is designed for easy installation on DIN rails.
1.
Fit the upper hook of the FP-I4C unit onto the DIN rail.
18
(1)
(1)
(1)
FP-I4C
(2)
FP-I4C