PDU8000 Modular Integrated PDC V1.0
User Manual
Main
Second-Level
Menu
Menu
About
Operating
Displays status of main route circuit breakers and branch circuit breakers, and surge
Status
protective status of each branch. You can tap the icon of the main route or a branch
to view its operating details.
Common
Displays common menus, including Branch Output 1, Branch Output 2, Branch
Functions
Output 3, and Branch Output 4. You can tap the submenus to enter the
corresponding screen.
a: The buzzer is enabled by default and after power-on.
b: Software V versions are displayed on the Version Details screen. To view software VBD
versions, hardware versions, and compile time of the PDU8000, tap the blank area in the table. Tap
the blank area again to return to the original screen.
Issue 07 (2019-04-15)
Third/Fourth-Level
Menu
Fault Report
Address Reset
Screen Calib.
Upload CA Cert
Upload Cert File
Version Details
E-labels
: indicates that the current operating status cannot be identified.
: indicates that the route is disconnected or abnormal.
: indicates that the route is closed or normal.
Enter the user name and password to log in to the Settings or Maint. screen. The default user name
is admin or operator, and the preset password is 000001. If you enter incorrect passwords for three
consecutive times, the account is locked for 5 minutes.
The main screen is displayed, and the system performs a forcible logout if you have not operated the
screen for 3 minutes.
Route 3 Output and Route 4 Output are optional. The menu items are displayed when you configure
the power distribution detection board.
Copyright © Huawei Technologies Co., Ltd.
Function
Enables you to download fault
information to a USB flash drive.
Enables you to assign different
addresses to the power
distribution monitoring board.
Enables you to calibrate the
touchscreen precision.
Uploads the CA certificate.
Uploads the Cert file.
b
Displays the software and
hardware information about the
PDU8000.
Displays the equipment E-label.
7 MDU Commissioning Guide
Preset
Value
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
62