Figure 5-19 Leveling the feet
Step 2 Remove the cabinet connecting kits from the rack.
Step 3 Secure the connecting kits in the connection positions on the front door using screws.
Step 4 Use the same method to secure the connecting kits in the connection positions on the rear
door.
Step 5 Repeat the procedure to combine other PDCs.
Issue 07 (2019-04-15)
Remove the screw from the supporting kit of the connecting kit to secure the connecting kit.
A PDC in the middle position has four connecting points on each of the front and rear doors. An end
PDC has two connecting points on each of the front and rear doors.
When combining cabinets, ensure that all the upper surfaces of the cabinets are on the same plane.