Danfuss VLT 5000 Series Manual page 10

Frequency converter
Table of Contents

Advertisement

According to international require-
ments
Rated input
current
Max. cross-section of copper cable to power
(380-415 V) [mm
Max. cross-section of copper cable to power
(440-460 V) [mm
Max. cross-section of aluminium cable to
power (380-415 V) [mm
Max. cross-section of aluminium cable to
power (440-460 V) [mm
Max. cross-section of copper cable to power
(380-415 V) AWG]
Max. cross-section of copper cable to power
(440-460 V) AWG]
Max. cross-section of aluminium cable to
power (380-415 V) AWG]
Max. cross-section of aluminium cable to
power (440-460 V) AWG]
Max. pre-fuses (mains)
Integral pre-fuses (softcharge circuit)
Integral pre-fuses (softcharge resistors)
Integral pre-fuses (SMPS)
Efficiency
Weight IP 00
Weight IP 20
Weight IP 54
Power loss at max. load
Enclosure
1. If UL/cUL is to be complied with, pre-fuses type
Bussmann FWH and FWX or similar must be
used. Pre-fuses type gR must be used for VLT
6350 - 6550 380-460 V. Fuses must be designed
for protection in a circuit capable of supplying a
maximum of 100,000 Amps ms (symmetrical),
500 V maximum.
2. American Wire Gauge.
3. Measured using 30 m screened motor cables at
rated load and rated frequency.
4. Min. cable cross-section is the smallest cable
cross-section allowed to be fitted on the termi-
nals. Always comply with national and local
regulations on min. cable cross-section.
5. Connection stud 2 x M12 / 3 x M12.
10
VLT
VLT type
I
[A] (400 V)
VLT,N
I
(460 V)
VLT, N
2
5 )
]
2
5 )
]
2
5 )
]
2
5 )
]
2 ) 5 )
2 ) 5 )
2 ) 5 )
2 ) 5 )
MG.56.A1.02 - VLT is a registered Danfoss trade mark
®
5000/6000 Series
6350
6450
6500
389
467
584
431
431
526
2 x 150
2 x 185
2 x 240
3 x 70
3 x 95
3 x 120
2 x 120
2 x 150
2 x 185
3 x 70
3 x 95
3 x 95
2 x 185
2 x 240
2 x 300
3 x 120
3 x 150
3 x 185
2 x 150
2 x 185
2 x 240
3 x 95
3 x 120
3 x 150
2x250mcm 2x350mcm 2x400mcm 2x500mcm
3 x 2/0
3 x3/0
3 x 4/0
2 x 4/0
2x300mcm 2x350mcm 2x500mcm
3 x 1/0
3 x 3/0
3 x 3/0
2x350mcm 2x500mcm 2x600mcm 2x700mcm
3 x 4/0
3x250mcm 3x300mcm 3x350mcm
2x300mcm 2x400mcm 2x500mcm 2x600mcm
3 x 3/0
3 x 4/0
3x250mcm 3x300mcm
630/600
700/700
800/800
15/15
15/15
15/15
12/12
12/12
12/12
5.0/5.0
0.97
480
515
560
595
630
675
605
640
685
7500
9450
10650
IP 00 / IP 20 / IP 54
6550
648
581
2 x 300
3 x 150
2 x 300
3 x 120
3 x 185
3 x 185
3x250mcm
3 x 4/0
800/800
30/30
12/12
585
700
710
12000