Mitsubishi Electric 800 Series Instruction Manual page 24

Plug-in option, relay output function
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 Adjusting the output terminal response level (Pr.418)
The response level of the output terminals can be delayed in a range of 5 to 50 ms. (Operation example for the RUN signal.)
RUN
Pr.418 = 9999
RUN
Pr.418 ≠ 9999
NOTE
• The response level is not adjusted while Pr.418 = "9999".
• When Pr.157 OL signal output timer is set for the Overload warning (OL) signal output, the OL signal is output when the
set time of (Pr.157 + Pr.418) elapses.
24
RELAY OUTPUT
OFF
ON
ON
Pr.418
Pr.418
Time
OFF