Air Intake / Combustion Products Discharge; Condensate Discharge - SBM AMC 12 Installers And Users Instructions

Modulating and condensing gas warm air heater
Table of Contents

Advertisement

AMC 78 to 116
5760035
O 200
O 130

3.5 Condensate discharge

The condensate discharge pipe is on the bottom of the heater. The siphon delivered with
the appliance shall be connected to this condensate discharge. A plastic tube Ø 40mm can be
connected to the siphon. The discharge system (not supplied by SBM) after the sifon
has to be ≥ Ø25mm and mounted with an inclination to the sewer. The advised inclination should be
minimum 30mm per meter. The horizontal length should not exceed 5 meters.
The condensate should be connected according to local and national regulations.
Do not let the condensate drip on the roof or roof edge outside the building, dangerous ice
can be formed in the winter. Condensate should be drained away to the sewer.
To be sure that the condensate can always flow out of the heater, an extra siphon should be
mounted before connecting to the sewer.
Before servicing the appliance, fulfil the siphon(s) with water in order to avoid
the dispersion of combustion products into the room.
If the appliance is mounted with an inclination between 0° and 45°, the condensate discharge will be
done in the front of the appliance (at the factory, the discharge is behind the appliance). Therefore, the
small sheet metal in the front of the heater can be removed and the pipe can be replaced to the front
of the heater.
!