Internal Battery Connection Procedure - Tripp Lite SmartOnline 3-Phase UPS Systems SU20KX Owner's Manual

3-phase ups systems
Table of Contents

Advertisement

Available languages

Available languages

6 – Internal Battery Connection

6-2 Internal Battery Connection Procedure

Place the UPS system in bypass (or turn it completely off) and turn
1
off the internal battery circuit breaker switch, located on the rear of
the UPS system.
Remove the battery access bezels, located on the front of the UPS
2
system.
3
Remove the battery cartridge fuses from each fuse block.
Disconnect the blue and white jumper cables attached to each fuse
4
block. Warning: When disconnecting the jumper cables, pull
them straight away from the fuse block with even force. Do not
wiggle them side-to-side, as this may damage the connector.
Remove the fuse block bracket. Note its orientation before
5
removal.