18

FAN Signal Wiring Concept

L
N
Motor input power
220-240 V~ 50 Hz
220 V~ 60 Hz
CAUTION
!
• If the motor is On/Off type, HI/MED/LOW wire have to connect as common.
For example, If you just connect HI wire to the motor(On/Off), motor is not operating
according to our control logic.
• High, Middle, Low wire from AHU Comm. Kit should not be connected directly to the
motor. Always use it as a motor for driving the relay contacts. Otherwise there is a risk of
damage to product or a fire.
[AHU]
M
R-HI
R-MED
(MCC Panel )
[AHU Comm. Kit]
R-LOW
Control power
220-240 V~ 50 Hz
220 V~ 60 Hz
Cable : Over CV 1.5 mm
Motor
M
Relay
Field Wiring
Factory Wiring
1