Lilytech ZL-7850A Manual

Lilytech ZL-7850A Manual

Humidity and temperature controller rich display

Advertisement

Quick Links

Z
L
Z
L

Feature

ZL-7850A is a temperature and humidity controller with rich display. IP65 level front panel protection,
convenient operation and easy installation. Suitable for control of incubator, climate chamber,
greenhouse, warehouse, and so on.

Specification

Power supply:
Input:
Sensor precision:
Setting range:
Display range:
Output:
Working environment:
Case dimension:
Drilling size:
Case materials:
Protection level:

Key Function

 Heat/cool control
 Humidify/dehumidify control
 Timer air exhaustion
 Timer and manual egg turning
 Temperature and humidity calibration

Display

-
7
8
5
0
A Humidity and Temperature Controller
-
7
8
5
0
A
Rich Display
Version
100 ~ 240Vac, 50/60Hz
One humidity and temperature sensor, wire length
Humidity ±3%/25℃ (ZL-SHr03A), ±2%/25℃
Humidity 0 ~ 80%RH; Temperature 0 ~ 65
Humidity 0 ~ 99%RH; Temperature -20 ~ 80
Temp. Output ≤ 5A,
Humi. Output and Fan Output ≤ 3A,
2 Egg turns ≤ 1A
-10 ~ 45
; ≤ 90% RH without dew
L78 x W34.5 x D71 (mm)
L 71 x W29 (mm)
PC + ABS, fireproof
IP65 (Front panel only)
Page 1. Total 5 pages
A1.2
(ZL-SHr05B); Temperature ±1%
 Temperature and humidity high limit protection
 Temperature and humidity limits alarm
 Alarm and protection when sensor fails
 Restore control when power supply returns
Suzhou Lily Tech. Co., Ltd.
2
meter

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZL-7850A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Lilytech ZL-7850A

  • Page 1 Rich Display Version A1.2 Feature ZL-7850A is a temperature and humidity controller with rich display. IP65 level front panel protection, convenient operation and easy installation. Suitable for control of incubator, climate chamber, greenhouse, warehouse, and so on. Specification Power supply: 100 ~...
  • Page 2 Suzhou Lily Tech. Co., Ltd. Icon Function Blink Heat output (R3) Energized Deenergized Deenergized because Cool output (R3) Energized Deenergized of delay protecting (ref. Humidify output (R2) Energized Deenergized 【t2】, 【h2】) Dehumidify output (R2) Energized Deenergized Energized Energized because of Multifunction fan output (R1) Deenergized periodically...
  • Page 3 Suzhou Lily Tech. Co., Ltd. Code parameter table: Factory Code Function Range Remark Default Temp. control mode H: heat; C: cool ℃ Temp. hysteresis 0.1 ~ 20 Time delay protection for Temp. load 0 ~ 30 min ℃ Temp. calibration -9.9 ~...
  • Page 4 Suzhou Lily Tech. Co., Ltd. Humidity control Humidify mode【h0 = H】 When Room humidity ≤ Set humidity (HP) -【h1】, and Humi. Output (R2) has stopped for【h2】, Humi. Output (R2) will be energized. When Room humidity ≥ Set humidity (HP), Humi. Output (R2) will be deenergized. Dehumidify mode【t0 = P】...
  • Page 5 Suzhou Lily Tech. Co., Ltd. Keypad lock Press〖S〗and〖P〗simultaneously for 3 seconds to lock the keypad, “Lo” displays for 3 seconds. When keypad locked, any keypress will not executed, but display “Lo”. Press〖S〗and〖P〗simultaneously for 3 seconds to unlock, “Un” displays for 3 seconds. Restore to factory default setting Press〖P〗and〖▲〗simultaneously for 3 seconds, “UnL”...