CIRCULATION SYSTEM DESIGN

Equipment room piping design is based on years of
experience with earth coupled heat pump systems.
The design eliminates most causes of system failure.
Surprisingly, the heat pump itself is rarely the cause.
Most problems occur because designers and installers
forget that a closed loop earth coupled heat pump
system is not like a household plumbing system.
Most household water systems have more than
enough water pressure either from the well pump or
the municipal water system to overcome the pressure
of head loss in 1/2 inch or 3/4 inch household
plumbing. A closed loop earth coupled heat pump
system, however, is separated from the pressure of the
household supply and relies on a small, low wattage
pump to circulate the water and antifreeze solution
through the earth coupling, heat pump and equipment
room components.
The small circulator keeps the operating costs of the
system to a minimum. However, the performance
of the circulator must be closely matched with the
pressure of head loss of the entire system in order
(Earth Coupled Ground Loop Applications)
to provide the required flow through the heat pump.
Insufficient flow through the heat exchanger is one of
the most common causes of system failure. Proper
system piping design and circulator selection will
eliminate this problem.
Bard supplies a work sheet to simplify head loss
calculations and circulator selection. Refer to
"Circulating Pump Work sheet" section in manual
2100-099.

COPPER WATER COIL APPLICATION

Copper water coils are available as a factory-installed
option. The unit model number will indicate the coil
option as the next to last character; "C" represents
a water coil constructed of copper material and "N"
represents a water coil constructed of cupronickel.
The cupronickel coil is suitable for all applications.
The copper coil is suitable for applications using
ground loop and cooling tower only and is not
recommended for open well application.

CLOSED LOOP

Manual 2100-738A
Page
51 of 71