ADJUSTMENTS

NOTE: MENU
JUMPER MUST
BE SET TO "ON"
TO CHANGE ANY
SETTINGS WITH
THE FRONT BUTTONS.
TO LOCK THE CO2
CONTROLLER MOVE
JUMPER TO "OFF" AFTER
IT HAS BEEN CONFIGURED
4-20mA
AN (ppm)
4
700
5
750
6
800
7
850
8
900
9
950
10
1000
11
1050
12
1100
13
1150
14
1200
15
1250
16
1300
17
1350
18
1400
19
1450
20
1500
(1) Damper should be fully closed at 700 ppm, if not Potentiometer R7 can be adjusted
clockwise (CW) to close it. If it is fully closed at 700 ppm or lower no adjustments required.
(2) Blade as referenced to the Blade Position Label.
FIGURE 23
CO
Control Configuration
2
Approc. Blade
Damper (1)
Position (2)
FULLY CLOSED
0
1
2
3
4
5
6
7
8
9
10
11
12
14
15
16
FULLY OPEN
17
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
JUMPERS MUST BE
POSITIONED AS SHOWN
FOR PROPER OPERATION
Settings Recommended
Default
RON
Not Used
ROF
Not Used
DSP
C
UNI
US
COL
700
COH
1500
TOL
Not Used
TOH
Not Used
See Instrution with Controller
BAR
For High Altitude Installations
CAL
Used for Field Calibration
CT
US
0
2000
MIS-3009A
MIS-3009 A
Manual 2100-738A
Page
31 of 71