Fault Finding - andrews ST XL Cylinder Series Installation And Service Manual

Cylinder range storage tanks, indirect 400ltr 500ltr 800ltr 1000ltr 1250ltr 1450ltr 2000ltr 2500ltr
Table of Contents

Advertisement

Fault finding

The fault finding chart will enable operational faults to be identified and their possible causes rectified. Any work carried
out on the Andrews water heaters and its associated controls MUST be carried out by a competent installer for
unvented water heating systems. In case of doubt contact the Andrews Water Heaters service department.
Table 12: Fault Finding guide
Fault
No hot water flow
Water from hot tap
is cold
Water discharges
from overflow visual
indicator
Water discharges
from the T&P relief
valve intermittently
Water discharges
from the T&P relief
valve continually
Performance has
deteriorated
28
Possible Cause
Mains water supply off
Strainer blocked
Cold water combination valve incorrectly
fitted
Indirect programmer set to central
heating only
Indirect boiler not working
Indirect thermal cut-out has operated
Indirect motorised valve not connected
correctly
INTERMITTENTLY
CONTINUALLY
Expansion relief valve faulty
Thermal control failure
NOTE: Water will be very hot
GRADUALLY
SUDDENLY
Remedy
Check and open stop cock/isolating valve
Turn off water supply, remove strainer and
clean
Check and refit as required
Check, set to domestic hot water programme
Check boiler operation. If fault is suspected
consult boiler manufacturer's instructions
Check, reset by pushing button on thermal cut-
out
Check operation of indirect thermostat
Check wiring and/or plumbing connections to
motorised valve
Incorrect pre-charge pressure for expansion
vessel
Check pressure from pressure reducing valve
Remove expansion relief cartridge from pressure
relief valve and check seating. If necessary fit
new cartridge
Check valve and replace if necessary
Switch off power to immersion heater(s) and
shut down boiler. DO NOT turn off water
supply. When discharge stops check all thermal
controls, replace if faulty
Check for scale build up in the DHW heat
exchanger
Check the operation of the blending valve.