24 Technical data
Operating temperat-
Free air circulation: 0...70 °C (32...158 °F)
ure
Dimensions
247 mm × 79 mm × 66.5 mm (9.72 in × 3.11 in × 2.62 in)
(L × W × D)
Mounting
35 mm mounting rail EN 50022, vertical or horizontal
Other features
UL approved (UL Listed according to UL
508 C)
Conformal coating as standard

Optical components

The specifications of the optic cable are as follows:
Storage temperature: -55 ... +85 °C (-67 ... +185 °F)
Installation temperature: -20 ... +70 °C (-4 ... +158 °F)
Maximum short-term tensile force: 50 N (11.2 lbf)
Minimum short-term bend radius: 25 mm (1.0 in)
Minimum long-term bend radius: 35 mm (1.4 in)
Maximum long-term tensile load: 1 N (3.6 ozf)
Flexing: Max. 1000 cycles
ABB drive products in general utilize 5 and 10 MBd (megabaud) optical components from
Avago Technologies' Versatile Link range. Note that the optical component type is not
directly related to the actual communication speed.
Note: The optical components (transmitter and receiver) on a fiber optic link must be of the
same type.
Plastic optical fiber (POF) cables can be used with both 5 MBd and 10 MBd optical
components. 10 MBd components also enable the use of Hard Clad Silica (HCS®) cables,
which allow longer connection distances thanks to their lower attenuation. HCS® cables
cannot be used with 5 MBd optical components.
The maximum lengths of fiber optic links for POF and HCS® cables are 20 and 200 meters
(65.6 ft and 656 ft) respectively.
BSFC-02C
BSFC-12C