Lennox VEP Series Installation & Operation Instructions page 44

Vrf systems outdoor units
Table of Contents

Advertisement

Lennox VRF Unit
(1)
For modular outdoor units, if there are multiple outdoor modules, then the master unit must be the first
outdoor module on the communication wire and should not connect with IDU (master unit is set by
SA8 of the outdoor main board).
(2)
For modular outdoor units, if there are multiple outdoor modules, then indoor units must be connected
with the last slave module of ODU (slave module is set by SA8 of the outdoor main board).
(3)
Communication wire and power cord must be separated.
(4)
Communication wire must be of proper length. Extension is not allowed.
(5)
IDUs must be connected in series. The last IDU must be connected with the communication matched
resistance (supplied in the list of ODU spare parts).
Fig.51
Fig.52
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents