5 - Installation
MULTICONTACT (or equivalents)
Installation of Multicontact connectors requires crimping to be carried out
with suitable equipment.
- Strip the cable to which you want to apply the connector (after verifying
that it complies with the connector limits)
2
4...6mm
5.5...9mm
- Apply the terminal to the conductor using suitable crimping pliers
- Insert the cable with the terminal into the interior of the connector, until
you hear the click indicating that the terminal is locked inside the con-
nector.
Click
- Firmly tighten the cable gland to finish the operation
2.5 Nm
- 47 -