Field Connections - Bryant 551B Series Installation, Start-Up And Service Instructions Manual

Single package rooftop electric cooling units
Table of Contents

Advertisement

NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in de-
tail ''A.'' Holes in base rails are centered around the unit center of
gravity. Use wooden top skid when rigging to prevent rigging straps
from damaging unit.
3. Weights do not include economizer. See Table 1 for economizer
weights.
CAUTION: All panels must be in place when
rigging.
IV. FIELD CONNECTIONS
A. External Trap Condensate Drain
The unit's
-in. condensate drain connections are located
3
4
on the bottom and end of the unit. Unit discharge connec-
tions do not determine the use of drain connections; either
drain connection can be used with vertical or horizontal
applications.
When using the standard end drain connection, make sure
the plug in the alternate bottom connection is tight before in-
stalling the unit.
To use the bottom drain connection for a roof curb installa-
tion, relocate the factory-installed plug from the bottom con-
nection to the end connection. See Fig. 7. The piping for the
condensate drain and external trap can be completed after
the unit is in place.
All units must have an external trap for condensate drain-
age. Install a trap at least 4-in. deep and protect against freeze-
up. See Fig. 8. If drain line is installed downstream from
the external trap, pitch the line away from the unit at 1 in.
per 10 ft of run. Do not use a pipe size smaller than the unit
connection.
Fig. 5 — Unit Leveling Tolerances
UNIT
551B
036
048
060
072
Fig. 6 — Rigging Details
B. Field Duct Connections
NOTE: The design and installation of the duct system must
be in accordance with NFPA standards for the installation of
nonresidence-type air conditioning and ventilating systems,
NFPA No. 90A or residence-type, NFPA No. 90B, and/or local
codes and ordinances.
Adhere to the following criteria when selecting, sizing and
installing the duct system:
1. Remove appropriate panels from unit to obtain either
horizontal or vertical discharge. If units are installed in
horizontal discharge applications, remove vertical dis-
charge duct covers, save screws, and install covers over
vertical duct openings.
2. Select and size ductwork, supply-air registers and return-
air grilles according to ASHRAE (American Society
of Heating, Refrigeration and Air-Conditioning Engi-
neers) recommendations.
—5—
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B
B-C
0.5
1.0
OPERATING
WEIGHT
''A''
Lb
Kg
in.
mm
435
197
73.69
1872
445
202
73.69
1872
465
211
73.69
1872
520
236
73.69
1872
A-C
1.0
DIMENSIONS
''B''
''C''
in.
mm
in.
mm
35.50
902
33.31
847
35.50
902
33.31
847
35.50
902
33.31
847
35.50
902
33.31
847