AIRFLOW
(Cfm)
0.1
Rpm
Bhp
1200
514
0.15
1300
545
0.18
1400
577
0.21
1500
609
0.26
1600
642
0.30
1700
675
0.36
1800
709
0.41
1900
743
0.48
2000
778
0.55
AIRFLOW
(Cfm)
1.0
Rpm
Bhp
1200
999
0.66
1300
1025
0.74
1400
1042
0.81
1500
1060
0.88
1600
1080
0.95
1700
1101
1.03
1800
1122
1.11
1900
1143
1.21
2000
1165
1.31
LEGEND
Bhp — Brake Horsepower Input to Fan
NOTES:
1. Boldface indicates a field-supplied drive is required. (See
Note 7.)
2.
indicates field-supplied motor and drive are required.
3.
indicates maximum usable bhp.
4. Maximum continuous bhp is 1.20. Extensive motor and electrical
testing on these units ensures that the full range of the motor can be
Table 11 — 551B048 Air Delivery — Horizontal Discharge Units
External Static Pressure (in. wg)
0.2
0.3
Rpm
Bhp
Rpm
Bhp
590
0.20
657
0.25
615
0.23
680
0.29
642
0.27
704
0.33
670
0.31
729
0.38
699
0.36
755
0.43
728
0.42
782
0.49
759
0.48
810
0.55
790
0.55
838
0.62
836
0.62
875
0.70
DIRECT-DRIVE MOTOR
External Static Pressure (in. wg)
1.1
1.2
Rpm
Bhp
Rpm
Bhp
1018
0.67
1036
0.68
1058
0.79
1090
0.84
1080
0.88
1118
0.95
1098
0.96
1136
1.04
1117
1.04
1153
1.12
1137
1.12
1172
1.20
1157
1.20
1192
1.29
1179
1.30
1214
1.39
1200
1.40
1235
1.49
DIRECT-DRIVE MOTOR
0.4
0.6
Rpm
Bhp
Rpm
723
0.30
828
744
0.35
849
766
0.39
870
788
0.44
892
811
0.49
913
836
0.55
935
860
0.62
957
886
0.69
980
913
0.77
1004
1.4
1.6
Rpm
Bhp
Rpm
1073
0.71
1109
1121
0.87
1159
1175
1.06
1206
1205
1.19
1258
1224
1.29
1287
1241
1.38
1307
1258
1.48
1323
1279
1.58
1341
1300
1.69
1361
utilized with confidence. Using your fan motors up to the ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected.
5. Values include losses for filters, unit casing, and wet coils.
6. Use of a field-supplied motor may affect wire sizing. Contact your
local representative to verify.
7. Motor drive range: 840 to 1185. All other rpms require field-supplied
drive.
8. Interpolation is permissible. Do not extrapolate.
9. Minimum allowable cfm is 300 cfm/ton.
—26—
0.7
Bhp
Rpm
Bhp
Rpm
0.42
876
0.49
924
0.47
895
0.54
940
0.52
915
0.59
959
0.58
936
0.65
980
0.64
957
0.72
1001
0.71
979
0.79
1023
0.78
1001
0.86
1044
0.86
1023
0.95
1066
0.94
1046
1.03
1088
1.8
Bhp
Rpm
Bhp
0.75
1138
0.79
0.90
1193
0.95
1.09
1244
1.12
1.30
1289
1.34
1.45
1337
1.56
1.56
1366
1.73
1.67
1385
1.86
1.78
1402
1.98
1.90
1419
2.10
0.8
Bhp
0.55
0.60
0.66
0.72
0.79
0.86
0.94
1.03
1.12