Trane CCUN 205-211 User Manual page 14

Chiller control system
Table of Contents

Advertisement

14
DynaView Interface
Table 2 - Circuit Level Operating Modes:
Circuit Level Mode
Top Level Mode
Stopped
Stopped Sub Modes
Diagnostic Shutdown - Manual Reset
Front Panel Circuit Lockout
Circuit Level Mode
Top Level Mode
Run Inhibit
Run Inhibit Sub Modes
Diagnostic Shutdown - Auto Reset
Condenser Pressure Limit
Circuit Level Mode
Top Level Mode
Auto
Auto Sub Modes
Circuit Level Mode
Top Level Mode
Waiting to Start
Waiting to Start Sub Modes
Circuit Level Mode
Top Level Mode
Running
Running Sub Modes
Description
The circuit is not running, and cannot run without
intervention.
Description
The circuit has been shutdown on a latching diagnostic.
The circuit is manually locked out by the circuit lockout setting
- the nonvolatile lockout setting is accessible through either
the DynaView or TechView.
Description
The given circuit is currently being inhibited from starting (and
running), but may be allowed to start if the inhibiting or
diagnostic condition is cleared.
Description
The circuit has been shutdown on a diagnostic that may clear
automatically.
The circuit is being inhibited from starting due to high
condenser pressure.
Description
The circuit is not currently running but can be expected to
start at any moment given that the proper conditions are
satisfied.
Description
No Circuit Sub-Modes
Description
The chiller is going through the necessary steps to allow the
lead circuit to start.
Description
No Circuit Sub-Modes
Description
The compressor on the given circuit is currently running.
Description
No Circuit Sub-Modes
CG-SVU02B-E4