Installation Instructions - Trane EXWA Installation Manual

Water-to-water water-source heat pump
Table of Contents

Advertisement

10
Installation
General Installation Checks
The checklist below is a summary of
the steps required to successfully in-
stall a unit. This checklist is intended to
acquaint the installing personnel with
procedures required in the installation
process. It does not replace the de-
tailed instructions called out in the ap-
plicable sections of this manual.
1 Remove packaging and inspect the
unit. Check the unit for shipping
damage and material shortage; file
a freight claim and notify appropri-
ate sales representation.
Note: The units have been tied to
the skid by (4) angle brackets. Re-
move these brackets from the unit
to slide unit from skid.
2
Verify the correct model, options
and voltage from the unit name-
plate.
3
Verify the installation location of
the unit will provide the required
clearance for proper operation.
4
Remove refrigeration access panel
and inspect the unit. Be certain the
refrigerant tubing has clearance
from adjacent parts.
WARNING
Hazardous
Voltage!
Disconnect all electric power,
including remote disconnects
before servicing. Follow proper
lockout/tagout procedures to
ensure the power can not be
inadvertently energized. Failure to
disconnect power before
servicing could result in death or
serious injury.
Main Electrical
5
Verify the power supply complies
with the unit nameplate specifica-
tions.
6
Inspect all control panel compo-
nents; tighten any loose connec-
tions.
7
Connect properly sized and pro-
tected power supply wiring to a
field-supplied/installed disconnect
switch and to the main power ter-
minal block (1TB1) in the unit con-
trol box for the 20-ton equipment,
or (1K1) for the 2-ton through 6-
ton equipment.
8
Install proper grounding wires to
an earth ground.
Note: All field-installed wiring must
comply with NEC and applicable local
codes.
Low Voltage Wiring (AC & DC)
Requirements
9
Connect properly sized control wir-
ing to the proper termination
points between the field supplied
thermostat and the terminal strip
located in the equipment control
box.
WSHP-SVX02A-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

GswdWpwd

Table of Contents