Table PD-28 — 20 to 75-Tons Electric Heat Air Temperature Rise
KW
Total
Input
MBh
4000
30
102.4
23.6
50
170.6
39.3
70
238.8
55.0
90
307 .1
110
375.3
130
443.6
150
511.8
170
580.1
190
648.3
Notes:
1. Maximum permitted air temperature rise; 20-30 tons (UL — 50 F) (CSA — 60 F), 40 — 60 ton (UL/CSA — 50 F).
2. Air temperature rise = kw x 3413 ÷ (scfm x 1.085)
3. All heaters on units provide 3 increments of capacity.
4. 200 and 230 volt electric heat rooftops require dual power supplies to the control box. All other rooftops have single power connections. See Electrical Data Section for
electrical sizing information.
Table PD-29— 90 To 130-Ton Electric Heat Air Temperature Rise
KW
Total
Input
MBh
24000
190
648.3
24.9
Notes:
1. Air Temperature = kw x 3413 ÷ (scfm x 1.085)
2. Only available in 460/60/3 and 575/60/3 voltages.