Trane PTAC-SVX01C-EN Installation, Operation And Maintenance Manual page 17

Packaged terminal air conditioner
Table of Contents

Advertisement

Step 9. Programmable
Settings
The controller has a total of six (7)
parameters that are user-
configurable:
1.
Vent Door Configuration
2.
Indoor Fan Cycle configuration
3.
Temperature Setpoint Limiting
configuration
4.
Energy Management Setpoint
Offset configuration
5.
Display Units configuration
6.
Indoor Temperature Calibration
7.
DH Offset
The interface module texts
"SETTING" and "STEP" provide user
feedback when the unit is in the
configuration mode. The number
directly above the word "STEP"
indicates the configuration step that
is being adjusted. The numbers
above the word "SETTING" (XX.x)
indicate the value of the parameter.
In order for the user to access the
configurable parameters, a digital
display module must be present.
The configuration set-up mode is
entered by pressing and holding the
"MODE" and "FAN" buttons
simultaneously for 5 seconds.
PTAC-SVX01C-EN
Installation
Table 9.
Set point configuration
Configuration
step
Step description
1
Ventilation Enable 0
2
Indoor fan cycle
Temperature
3
Setpoint Limits
4
Energy
Management
Display units
5
6
Indoor
Temperature
Calibration
7
DH offset
Configuration
setting
Setting description
Ventilation is disabled
1 (default)
Ventilation is enabled
0 (default)
Cycle with compressor
continuously, OFF in OFF mode
1
ON continuously, HIGH in OFF
mode
2
0 (default)
cool 50 - 90°F, heat 50 - 90°F
1
cool 55 - 90°F, heat 50 - 85°F
2
cool 60 - 90°F, heat 50 - 80°F
3
cool 65 - 90°F, heat 50 - 75°F
Default: 10°F (5.5°C)
Range: 0 to 20°F
(0.0 to 10.0°C)
Resolution: 1.0°F
(0.5°C)
0 (default)
IP (English)
1
SI (Metric)
Default: 0°F (0.0°C)
Range: -9 to 9°F
(-5.0 to 5.0°C)
Resolution: 1.0°F
(0.5°C)
Default: 1°F (0.5°C)
Range: 0 to 2°F
(0.0 to 1.0°C)
Resolution 1.0°F
Value of zero disables DH.
(0.5°C)
17