Trane PTAC-SVX01C-EN Installation, Operation And Maintenance Manual page 11

Packaged terminal air conditioner
Table of Contents

Advertisement

Table 3.
Electric heat capacity and electrical data, models PTEE and PTHE
Electric
heater
# of
(ii)
Voltage
Size (kW)
stages
230/208
2.0/1.6
1
230/208
3.0/2.4
1
230/208
5.0/4.0
1
265
2.0
1
265
3.0
1
265
5.0
1
(i)
All heat pumps have electric heat.
(ii)
Minimum voltage on 230/208 volt models is 187 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 239 volts; max-
imum is 292 volts.
(iii)
Total watts for 7,000 and 9,000 Btu models; add 70 watts for 12,000 and 15,000 Btu models.
(iv)
Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
(v)
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-
style time delay fuses.
Table 4.
Power receptacle configurations
Unit
Voltage
230/
230/
Rating
208
208
Unit plug
Plug amp
15
20
rating
NEMA
6-15P
6-20P
designation
Receptacle
Receptacle
20
20
amp rating
NEMA
6-20R
6-20R
designation
PTAC-SVX01C-EN
Installation
Nominal heating
Btu/h at
Btu/h at
Total
(iii)
230/208V
265V
watts
6,800/
-
2000/
5,500
1600
10,200/
-
3000/
8,200
2400
17,100/
-
5000/
13,700
4000
-
6,800
2000
-
10,200
3000
-
17,100
5000
230/
208
265
265
30
15/20
30
6-30P
7-15P/7-20P
7-30P
30
20
30
6-30R
7-20R
7-30R
(i)
Building circuit requirement
Unit
total
Minimum
Maximum
(iv)
amps
ampacity
protection
8.9/7.9
11.4
13.4/11.8
17
22.2/19.7
28
7.7
9.8
11.6
14.7
19.3
24.4
(v)
Plug
15
6 - 15 P
20
6 - 20 P
30
6 - 30 P
15
7 - 20 P
15
7 - 20 P
25
7 - 30 P
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents