PELLET BURNER
Pell Mega series
TECHNICAL PASSPORT
INSTALLATION and OPERATION MANUAL
FOR AUTHORIZED INSTALLER / SERVICE SHOP
Version i2.2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BURNiT Pell Mega Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Sunsystem BURNiT Pell Mega Series

  • Page 1 PELLET BURNER Pell Mega series TECHNICAL PASSPORT INSTALLATION and OPERATION MANUAL FOR AUTHORIZED INSTALLER / SERVICE SHOP Version i2.2...
  • Page 3: Table Of Contents

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TABLE OF CONTENTS EXPLANATION OF SYMBOLS AND SAFETY INSTRUCTIONS ......4 1.1. Explanation of symbols ................. 4 1.2. Requirements to burner installation room ........... 4 1.2.1. Instructions to burner installer ..............4 1.2.2. Instructions to installation user ..............5 1.2.3.
  • Page 4: Explanation Of Symbols And Safety Instructions

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 1. EXPLANATION OF SYMBOLS AND regulations must be observed: SAFETY INSTRUCTIONS • local construction regulations installation, air supply and exhaust 1.1. Explanation of symbols gas extraction as well as chimney connection. Important CAUTION! • regulations and norms concerning the recommendation warning fitting of the heating installation with...
  • Page 5: Instructions To Installation User

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL • Do not install the burner in sleeping It is mandatory to assure a premises.  backup power generator of • Do not connect the burner to any other corresponding rated power! air-intake systems . (see 12.2) •...
  • Page 6: Minimum Clearances For Installation And Combustibility Of Construction

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL combustion chamber tube and external CAUTION! Hot surface! Risk of burns if you touch the tube. On the upper part of the burner running system. Burner housing, there is a feeder chute to which the body and flange are hot surfaces pellet auger is attached.
  • Page 7: Fuel

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL depending the configured point when the power interruption intervals; occurred. 3) controls the operation of the • STB - emergency thermostat (with circulation pump of the central probe inserted into the socket of the heating; boiler).
  • Page 8: Transportation Of The Burner

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL Fuel efficiency. High combustion 4. TRANSPORTATION OF THE PELLET BURNER efficiency also determined consistently low moister content of When loading, transporting pellets (consistently under 10% as unloading of the device appropriate opposed to 20% to 60% moisture content safety equipment must be used in of the logs).
  • Page 9: Storage Of The Burner

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL any of the above items are missing, in their original packaging. The storage period is not more than 2 years from date contact your supplier. of manufacture. It is recommended that every burner is tested before installation. Quality and safety of the burner must be confirmed by a test mentioned in the warranty card.
  • Page 10: Connecting The Burner To Pellet Auger And Fuel Hopper

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL Table 1 European Certification of Wood Pellets for Heating Purposes Parameters Units ENplus-A1 ENplus-A2 EN-B 6 (± 1) 6 (± 1) 6 (± 1) Diameter 8 (± 1) 8 (± 1) 8 (± 1) Lenght 15 ≤...
  • Page 11: Connecting The Burner To The Mains Power Supply

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 7.2. Connecting the pellet burner to the It is mandatory to assure a  mains power supply backup power generator of corresponding rated power! (see Such connection must be 12.2)  performed by a technician / service shop authorized for such Improper cable connections may operations. damage the regulator! Caution! ELECTRIC SHOCK The device may be damaged if HAZARD! struck by a lightning. Make sure ...
  • Page 12 TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL Inputs Outputs Group 1 FM Fan main RT Room thermostat FSG Fan smoke gases PS Photo sensor Screw fuel RB Temperature sensor at the top of Screw burner the buffer Pump heating Boiler PWH Pump water heater Group 2 IGN Igniter WH Water heater...
  • Page 13: Trouble-Shooting

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 7.3. Trouble - shooting Table 2. Fault Cause Solution 1. Low temperature in 1.1. Immediately consult your the boiler on which 1.1. Inadequate sizing and/ installer about the problem. the burner is installed. or combination of heating Mount the supplied filling and Unable reach...
  • Page 14: Operation Of Burner Burner

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 8. BURNER OPERATING set by the command block. The cleaning cycles can be additionally adjusted as 8.1. Ignition. well as their repeat rate depending on After the start up of the burner from the load of the burner. the control panel, the main pellet auger conveys certain amount of fuel from the 8.4. Installer prescriptions regarding...
  • Page 15: Controller Unit

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL  Failure to observe the installation and operating requirements described in the manual and the service booklet voids the warranty. Type of Procedure Duty of: maintenance Daily Cleaning the movable grate. User User / Complete disassemble and clean the burner. To Monthly replace all the trimmings. Installer Dismantle the whole burner. Clean each part. Replace Once per year Installer all gaskets with new ones.
  • Page 16 TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL Display symbols explanation: The notice "Hi" appearance on the Auto Clean symbol appears in right screen where boiler upper part of display. Active auto temperature is displayed means that measured Boiler body cleaning symbol means boiler automatic temperature is above 120°C.
  • Page 17: User Menu

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL Factory setting - Alarms there is no signal from room termostat or there is non-fullfilled requirement for Reverse fire Alarm (when DHW, the burner will fire up. the thermostat contact RB ALARM In “CH + DHW” mode when DHW input is open) (Domestic hot water) requirement is SENSOR...
  • Page 18 TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL From this menu Use UP and DOWN you can preset arrow keys in Set buffer tank Date menu to set circulation pump the date. switch-on Use UP and DOWN arrow keys in Contrast switch-off temperatures provided such menu to adjust the LCD display backlight heating installation scheme (with buffer level.
  • Page 19: Installer Menu

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 9.2.2. Burner star up "Switch mode" activity periods. Use the arrow keys to set time (HH:MM). Use “Enter” button to Burner start-up. After pressing the checkmark desired time period option. “F” button option check-marked, using „navi- the controller will maintain DHW gation arrows”, the temperature as a priority.
  • Page 20 TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL The service menu indicates that the automatic cleaning comprises only system is active. uniquely 9.3.2. Ignition setup parameters with In this submenu direct impact on you can set the boiler combustion number of attempts process, as well as (Retries) to ignite heating the burner and the...
  • Page 21 TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL Select the desired option using the Example: with the period set at 10 navigation arrows. Use the „Enter” seconds, the pellet auger runs for 2 button to open the next parameter. Use seconds feeding pellets in the burner, and is off for 8 seconds.
  • Page 22 TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL (Feed), time interval at which these in minutes with a maximum duration of 180 minutes. pellets are fed (Cycle) and fan output as a percentage value (FAN). If within a set time (20 minutes) the temperature in the boiler does Example: with the period set at 10 not decrease, the burner enters into...
  • Page 23 TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL Select the desired option using the fuel in the burner, the internal auger will navigation arrows. Use the „Enter” run for 30 seconds, if the setting is (Duty button to open the next parameter. Use 300% - see picture) Duty parameter can be changed from 0% up to 300%.
  • Page 24: Setting Output Modes Of Operation Of The Pellet Burner

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL navigation arrows. Use the „Enter” 3) CH – Central Heating pump 4) DHW – Domestic Hot Water pump button to open the next parameter. Use 5) Ign – Ignition button to open the next page 6) CM –...
  • Page 25: Burner Output Adjustment

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL the flexible pipe is attached. 56,6 is the amount of pellets in grams Filling of the pellet auger is necessary fed by the auger per 1 second. This way when the fuel in the hopper has been the output mode can be changed and depleted or when fuel has been changed.
  • Page 26: Warranty Terms

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 11. WARRANTY TERMS Important: You use a burner whose carbon footprint values The warranty terms are described in the are approximately (СО = 100 Service booklet included in the supply. ppm), which is 2.5 times lower than the maximum allowed limits for harmful emissions in the EU Member States. Thus...
  • Page 27 TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL Table 3 Pell 300 Mega Pell 500 Mega Actuator Parameter value Service code 00000012 300 sec Cleaning Setup Cleaner 1 sec P On start Use Cleaner Cleaner P On Stop Retries Ignition Setup Feed 30 sec 35 sec Heater 3 min Ignition Setup 8 min...
  • Page 28: Technical Features

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 12. TECHNICAL FEATURES OF PELLET BURNER Pell Mega 12.1. Elemets of pellet burner Pell Mega Diagram 7. Elemets of pellet burner Pell Mega 1. Pellet burner Pell Mega 5. Control unit 2. Auger flexible pipe connection 6. Burner housing 3. Auger` motor 7.
  • Page 29: Technical Parameters

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 12.2. Technical parameters Table 4 Pell 300 Mega Pell 500 Mega Nominal heat output Min. / Max. heat output 90÷300 150÷500 Average ~ 980 ~ 1540 Firing-Up mode power Operate mode ~ 419 ~ 550 consumption Electric power supply V/Hz ~220/50 ~220/50 Height H...
  • Page 30: Recycling

    TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL 13. RECYCLING AND WASTE DISPOSAL Expired appliances must be collected separately from other recyclable waste Submit all packaging material for recycling containing substances hazardous to according to the local regulations and health and environment. Both metal and requirements.