2 EQUIPMENT HANDLING

2.1 Door Sensor

Inside the enclosure at the upper right is a door sensor to indicate when the door is open or closed. If the door is open for
more than 60 seconds, a fault is indicated and the enclosure is disconnected from the DC bus.

2.2 Power Chassis Assembly

The power chassis assembly (PCA) is a 4U enclosed section that controls the connection of the battery enclosure to the
DC bus. The PCA monitors each battery module's voltage and temperature to ensure operation within the manufacturer's
specified limits throughout the life of the product.
IMPORTANT! Operation of the Vertiv™ HPL Lithium-Ion Energy Storage System outside its recommended
environmental or power limits may void the warranty.
Figure 1.2 Power Chassis Assembly
Table 1.4 Power Chassis Assembly Descriptions
ITEM
NAME
S1 maintenance disconnect with lock-out,
1
tag-out feature
Service power input jack (120VAC
2
50/60Hz)
3
RUN/SERVICE key switch
Control power breaker (CTL PWR) and
4
shunt trip
5
Battery (BATT) interface
6
100BT interface
2 Equipment Handling
DESCRIPTION
Used to isolate the battery rack from the DC bus.
Warning!: Do not operate when the CTL PWR BREAKER is closed, except as specifically directed
when logged in to the service console.
For use by Vertiv™ service personnel only. Provides control power for servicing the unit when battery
power is unavailable.
For use by Vertiv service personnel under guidance from tech support only.
Interrupts control power from the battery.
Communications connection to battery modules.
Ethernet interface for Modbus/TCP.