Vertiv HPL Operation Manual page 28

Lithium-ion energy storage system
Hide thumbs Also See for HPL:
Table of Contents

Advertisement

Table 3.3 Enclosure Data Descriptions (continued)
DATA
INPUT
DESCRIPTION
REGISTER
Enclosure 7
31605
Status 2
Enclosure 7
31607
Status 3
Enclosure 7
31618
Target SOC
Enclosure 7
Percent
31619
Charged
Enclosure 7
Runtime
31620
Remaining
Enclosure 7 DC
31621
Bus Voltage
Enclosure 7 DC
31622
Power
Enclosure 7
Battery
31623
Voltage
Enclosure 7
Battery
31624
Current
Enclosure 7
Battery
31625
Temperature
Min
Enclosure 7
Battery
31626
Temperature
Max
Enclosure 7
Battery Cell
31627
Voltage Min
Enclosure 7
Battery Cell
31628
Voltage Max
Enclosure 7
Temperature
35301
Values per
Battery
Enclosure 7
Battery Temp
35302
1
22
#
REFERENCE#
OF
SCALE
REG
1604 (0x644h)
2
1
1606 (0x646h)
2
1
1617 (0x651h)
1
10
1618 (0x652h)
1
10
1619 (0x653h)
1
1
1620 (0x654h)
1
1
1621 (0x655h)
1
1
1622 (0x656h)
1
10
1623 (0x657h)
1
10
1624 (0x658h)
1
10
1625 (0x659h)
1
10
1626 (0x65Ah)
1
1000
1627 (0x65Bh)
1
1000
5300
1
1
(0x14B4h)
5301
1
10
(0x14B5h)
UNITS
NOTES
See Enclosure 1 Status 2.
See Enclosure 1 Status 3.
%
Range: 0 - 1000
%
Range: 0 - 1000
sec
Range: 0 - 1800
VDC
Range: 380 - 600
kW
Range: -32768 - 32768
VDC
Range: 0 - 65535
A
Range: -32768 - 32768
°C
Range: -3000 - 3000
°C
Range: -3000 - 3000
VDC
Range: 0 – 6000
VDC
Range: 0 – 6000
Range: 1 - 10
°C
Range: -3000 - 3000
Vertiv™ | Vertiv™ HPL Lithium-Ion Energy Storage System Operation Guide

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents