5-2-4 MODE3

(Mode for setting of each parameter for serial communication (RS-485))
<MODE>+< V >
Station number setting mode
Mode defines an individual station no. for each unit when two or more units communicate via
serial communication (RS-485).
・It can be set the range of 01 to 99.
Transmission speed (Baud rate) setting mode
Mode defines serial communication (RS-485) transmission speed. Define the transmission
speed according to the master's (PLC etc.).
・Select from 38400/19200/9600/4800/2400【bit/s】.
Transmission format setting mode
Mode defines serial communication (RS-485) transmission format (Data length, Parity). Define
the transmission format according to the master's (PLC etc).
・Select from 8bit-o/7bit-n/7bit-E/7bit-o/8bit-n/8bit-E for MEWTOCOL type.
8bit-o/8bit-n/8bit-E for MODBUS type.
"n(none)" means parity is not available.
"E(Even)" means parity is even number.
"o(odd)" means parity is odd number.
Response time setting mode
MODE defines serial communication (RS485) response time of main unit.
When command is received, it sends response after setting response time passes.
・It can be set the range of 5 to 99ms.
Station number setting mode
・ Enter the station number using <kW/kWh>, < A >.
・Station number can be entered the range of 01 to 99.
Transmission speed setting mode
・ Press <kW/kWh> to change transmission speed.
・ Transmission speed is selected from
Transmission format setting mode
・ Press <kW/kWh> to change transmission format
(Data length / Parity).
・ Transmission format is selected from
8bit-o→7bit-n→7bit-E→7it-o→8bit-n→8bit-E.
・ n: not available E: even number o: odd number
14
R E S P
Normal display
MODE display
19200→9600→4800→2400→38400.
N O .
S P 
F  T
↓ <MODE>
↓ < V >
Factory setting / Display
↓ <SET>
Factory setting / Display
↓ <SET>
Factory setting / Display
↓ <SET>