Refrigerant System Diagram; Troubleshooting - Mitsubishi Electric CITY MULTI PKFY Series Technical & Service Manual

Wall mounted, split-type, heat pump air conditioners
Hide thumbs Also See for CITY MULTI PKFY Series:
Table of Contents

Advertisement

7

REFRIGERANT SYSTEM DIAGRAM

PKFY-WL10VLM-E.TH
PKFY-WL20VLM-E.TH
PKFY-WL32VLM-E.TH
Heat exchanger
Room temperature
detection thermistor TH21
8

TROUBLESHOOTING

8-1. HOW TO CHECK THE PARTS
PKFY-WL10VLM-E.TH
PKFY-WL20VLM-E.TH
PKFY-WL32VLM-E.TH
Parts name
Room temperature
Disconnect the connector then measure the resistance with a tester.
detection thermistor (TH21)
(At the ambient temperature 10 to 30:)
Pipe temperature detection
thermistor/liquid (TH22)
Normal
Pipe temperature detection
4.3 to 9.6 k"
thermistor/gas (TH23)
Vane motor (MV1)
Measure the resistance between the terminals with a tester. (At the ambient temperature 25:)
7
Sky Blue
M
-9
10
9
Sky Blue
Red-Sky Blue
Red
10
Sky
Sky
Blue
Blue
Connector(CNV)
6
8
pin No.
Vane motor
Measure the resistance between the terminals with a tester. (At the ambient temperature 25:)
(Lower (MV2))
2
Sky Blue
M
5-4
4
Sky Blue
Red-Sky Blue
Red
5
Sky
Sky
Blue
Blue
Connector(CNV)
1
3
pin No.
Fan motor (MF)
Refer to "8-1-3. DC Fan motor (fan motor/indoor controller board)
Flow control valve
Disconnect the connector then measure the resistance between terminals with a tester.
(FCV)
CN8A
Refer to the next page for details.
Yellow
1
Orange
2
Red
3
Green
4
1-5
M
Blue
5
Yellow-Blue
Purple
FCV
6
(Optional parts)
White
7
Gray
8
Drain pump (DP)
1 Check if the drain float switch works properly.
2 Check if the drain pump works and drains water properly in cooling operation.
3 If no water drains, confirm that the check code 2502 will not be displayed 10 minutes after the operation starts.
1
RD
Note: The drain pump for this model is driven by the internal DC motor, so it is not possible to
2
VT
3
BK
Normal
(Optional parts)
Red–Black: Input 13 V DC → The pump motor starts to rotate.
Drain float
Measure the resistance between the terminals with a tester.
switch (FS)
State of moving part
Moving part
1
2
3
(Optional parts)
4
OCH711
PKFY-WL15VLM-E.TH
PKFY-WL25VLM-E.TH
PKFY-WL40VLM-E.TH
Pipe temperature detection
thermistor/ inlet
TH22
Manual air purge valve
Pipe temperature detection
thermistor/ outlet
TH23
PKFY-WL15VLM-E.TH
PKFY-WL25VLM-E.TH
PKFY-WL40VLM-E.TH
Refer to "8-1-1. Thermistor".
Normal
-8
-7
10
10
Red-Sky Blue
Red-Sky Blue
300 " ±7%
Normal
5-3
5-2
Red-Sky Blue
Red-Sky Blue
300 ±26.3 "
Normal
2-5
3-5
Orange-Blue
Red-Blue
55 " ±5.6 " (at 25℃)
measure the resistance between the terminals.
Normal
Other than short
UP
Short
Open
Other than open
DOWN
Short
Other than short
Water inlet
connection
Model
Item
Water inlet
Water outlet
Water outlet
connection
Check points
-6
10
Red-Sky Blue
5-1
Red-Sky Blue
Abnormal
4-5
Green-Blue
Open or short
Drain float switch
Abnormal
connector terminal
1(+) – 2(-)
1(+) – 2(-)
3(+) – 4(-)
19
Unit: in
PKFY-WL10/15/20/25/32/40VLM-E
Rc3/4 screw
Rc3/4 screw
Switch
Magnet
Moving
Part