3-2. ELECTRICAL PARTS SPECIFICATIONS
Service ref.
Symbol
Parts name
Room temperature
detection thermistor
Pipe temperature
detection thermistor/liquid
Pipe temperature
detection thermistor/gas
Fuse
(Indoor controller board)
Fan motor
(with thermal fuse)
Vane motor
(Upper)
Vane motor
(Lower)
Power supply terminal
block
Transmission terminal
block
MA-Remote controller
terminal block
* Refer to WIRING DIAGRAM for the supplied voltage.
3-3. SOUND PRESSURE LEVEL
PKFY-WL▪VLM-E
Measurement location
* Measured in anechoic room.
OCH711
PKFY-WL10VLM-E.TH
PKFY-WL15VLM-E.TH
PKFY-WL20VLM-E.TH
PKFY-WL25VLM-E.TH
TH21
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
TH22
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
TH23
Resistance 0:/15k", 10:/9.6k", 20:/6.3k", 25:/5.4k", 30:/4.3k", 40:/3.0k"
FUSE
MF
MV1
MV2
TB2
TB5
TB15
1m
T3.15AL250V
8 X 30W / RC0J30-QD
MSFBC20 DC12V
NSEK302 DC12V
(L, N, ;) Rated to 250V 20A *
(M1, M2, S) Rated to 250V 20A *
(1, 2) Rated to 250V 10A *
Sound pressure level at anechoic room : Low-Middle2-Middle1-High
Service Ref.
PKFY-WL10VLM-E.TH
PKFY-WL15VLM-E.TH
PKFY-WL20VLM-E.TH
PKFY-WL25VLM-E.TH
PKFY-WL32VLM-E.TH
PKFY-WL40VLM-E.TH
13
PKFY-WL32VLM-E.TH
PKFY-WL40VLM-E.TH
Sound pressure level dB (A)
22-26-28-30
22-26-29-32
22-28-33-36
22-30-36-41
29-34-38-41
30-36-41-45