Remote Controller Installation - Fujitsu ARU30RGLX Installation Manual

Indoor unit, duct type
Hide thumbs Also See for ARU30RGLX:
Table of Contents

Advertisement

3. 8. 2. Connection cable preparation
■ Connection cable
Keep the earth (ground) wire longer than the other wires.
Earth (ground)
wire
■ Remote controller cable
For 2-wire type
1-3/16 in (30 mm)
3. 8. 3. How to connect wiring to the terminals.
(1) Use ring terminals with insulating sleeves as shown in the fi gure below to connect to
the terminal block.
(2) Securely crimp the ring terminals to the wires using an appropriate tool so that the
wires do not come loose.
(3) Use the specifi ed wires, connect them securely, and fasten them so that there is no
stress placed on the terminals.
(4) Use an appropriate screwdriver to tighten the terminal screws.
Do not use a screwdriver that is too small, otherwise, the screw heads may be
damaged and prevent the screws from being properly tightened.
(5) Do not tighten the terminal screws too much, otherwise, the screws may break.
(6) See the table below for the terminal screw tightening torques.
Use ring terminals and tighten the terminal screws to the specifi ed torques, otherwise,
abnormal overheating may be produced and possibly cause serious damage inside the
unit.
Tightening torque [lbf·in (N·m)]
M4 screw
11 to 16 (1.2 to 1.8)
Screw with
special washer
Wire
Ring
terminal
Terminal blocks
3. 8. 4. Connection wiring
• Be careful not to mistake the power supply cable and connection wires when install-
ing.
• Install so that the wires for the remote controller will not come in contact with other
connection wires.
(1) Remove the control box cover and install each connection wire.
Loosen the screws. (3 locations)
Control box cover
Lock nut
(Locally purchased)
Attach the conduit connector on the wiring connecting port.
(The grommet edging and the connection cable clamp are
not used.)
Conduit connector
Ring terminal
Sleeve
WARNING
Screw with
special
washer
Wire
Ring
terminal
CAUTION
Conduit connector
(Locally purchased)
■ Connection cable
Earth (ground)
■ Remote controller cable
2-wire type
Red
Remote controller
*Earth (Ground) the remote controller if it has a earth (ground) wire.
(2) After wiring is complete, secure the remote controller cable and connection cable
with the wire clamper or cable tie.
Cable tie (medium)
(Accessory)
Remote controller cable
(3) Seal the cable outlet or other gaps with putty to prevent dew condensation or insect
from entering the electric control box.
(4) Replace the control box cover.
• Do not bundle the remote controller cable, or wire the remote controller cable in par-
allel, with the indoor unit connection wire (to the outdoor unit) and the power supply
cable. It may cause erroneous operation.
• Tighten the indoor unit connection wire and power supply indoor and outdoor unit,
terminal board connections fi rmly with the terminal board screws. Faulty connection
may cause a fi re.
• Connect the indoor unit connection wire by matching the numbers of the outdoor and
indoor units terminal board numbers as shown in terminal label.
• Be sure to refer to the connection diagram for the correct fi eld wiring. Wrong wiring
causes malfunction of the unit.
(5) Fix the conduit with the supporters as shown below.
Conduit (Power supply cable)
Indoor unit
30 in
54 in
(756 mm)
(1,361 mm)
or less
or less

3. 9. Remote controller installation

To install and set the remote controller, refer to the installation manual of the remote
controller (wired type).
Control line
Power line
Conduit
connector
Outdoor
unit
White
Remote
controller
cable
Wire clamper
Control box
Connection cable
(to outdoor unit)
CAUTION
Supporter
54 in
54 in
(1,361 mm)
(1,361 mm)
or less
or less
En-9

Hide quick links:

Advertisement

Table of Contents
loading