4. OPTIONAL INSTALLATION WORK

4. 1. Optional kit installation

Regulation of cable differs from each locality, refer in accordance with local rules.
CN8 (Remote sensor)
Y1
Y1
Y2
Y2
Y3
Y3
1
1
2
2
Terminal
(External in)
This air conditioner can be connected with the following optional kits.
For details on how to install optional parts, refer to the installation manual included in each
item.
Connector No.
CN48
CN8
CN47*1
CN65*2
*1: For external output terminal setting, refer to Function No.60 in "6. FUNCTION SETTING".
*2: Other options (WLAN adapter, converters, etc.) may be available by using the optional
External input and output PCB.

4. 2. External input and output

4. 2. 1. External input
• Indoor unit functions such as Operation/Stop or Forced stop can be
done by using indoor unit terminals.
• "Operation/Stop" mode or "Forced stop" mode can be selected with
function setting of indoor unit.
• A twisted pair cable (22 AWG) should be used. Maximum length of
cable is 492 ft. (150 m).
• Use an external input and output cable with appropriate external
dimension, depending on the number of cables to be installed.
• The wire connection should be separate from the power cable line.
● Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal.
*1
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
■ Operation behavior
● Input signal type
ON
Edge
OFF
When function setting is "Operation/Stop" mode 1.
Input signal
OFF → ON
Operation
ON → OFF
Stop
When function setting is "Forced stop" mode.
Input signal
OFF → ON
Forced stop
ON → OFF
Normal
* When the forced stop is triggered, indoor unit stops and Operation/Stop operation by a
remote controller is restricted.
En-10
WARNING
CN48
CN65
CN47
(IR receiver)
(External in/out PCB)
(External out)
Option type
IR receiver (UTY-LBTUM)
Remote sensor (UTY-XSZX)
Connect wire (UTY-XWZXZG)
External input and output PCB (UTY-XCSX)
PCB
Terminal
(External in)
Command
Command
When function setting is "Operation/Stop" mode 2.
Input signal
OFF → ON
ON → OFF
4. 2. 2. External output
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 82 ft. (25 m).
• Use an external input and output cable with appropriate external dimension, depending
on the number of cables to be installed.
• Output voltage: Hi DC12V±2V, Lo 0V.
• Permissible current: 50mA
■ Output select
● When interlocking with external device
Connected
device
● When displaying "Operation/Stop"
LED
Connected device
■ Operation behavior
*If function setting "60" is set to "00"
Function setting
Terminal
60
Connected device
4. 2. 3. Connection methods
■ Wire modifi cation
• Remove insulation from wire attached to wire kit connector.
• Remove insulation from locally purchased cable. Use crimp type insulated butt
connector to join fi eld cable and wire kit wire.
• Connect the wire with connecting wire with solder.
IMPORTANT: Be sure to insulate the connection between the wires.
Locally purchased
Solder and insulate the connected parts.
• Connecting wires to the terminals.
Use ring terminals with insulating sleeves to connect to the terminal block.
• Connection terminals and wiring arrangement
In following fi gure, all the possible connections are done for description.
In actual installation, connections will differ according to each installation requirements.
Command
Operation
Stop (R.C. disabled)
Relay (locally purchased)
or
Resistor
Status
Stop
00
Operation
OFF
01 - 05
ON
Stop
06
Operation
OFF
07 - 08
ON
Normal
09
Error
Indoor unit fan stop
10
Indoor unit fan operation
External heater OFF
11
External heater ON
Option parts
External output wire
PCB
CN47
PCB
CN47
Output voltage
0 V
DC 12 V
0 V
DC 12 V
0 V
DC 12 V
0 V
DC 12 V
0 V
DC 12 V
0 V
DC 12 V
0 V
DC 12 V