Standard Specifications - Toshiba Adjustable Speed Drive H3 Operation Manual

Variable torque adjustable speed drive
Table of Contents

Advertisement

Standard Specifications

ITEM
Principal
Control System
Control
Output voltage regulation Same as power line.
Specifications
Output frequency
Frequency setting
Frequency accuracy
Voltage/frequency
characteristics
PWM carrier frequency
Transistor type
Output voltage regulation Drive can be programmed to fix max. output volts, let max. float with
Dynamic braking
Frequency
Input signals
Set point control (PID)
Operating
Accel/decel time
functions
Forward or reverse run
Jogging run
Multispeed run
Retry
Soft stall
Automatic restart
Pattern Run
DC injection braking
Upper/Lower limit
Frequency jump
Edit function
Blind function
User-defined defaults
*
Consult the factory for applications above 80 Hz.
TOSHIBA
STANDARD SPECIFICATIONS
Sinusoidal PWM control
0.01 to 400 Hz (0.1 to 80Hz default setting)*. 800 Hz operation
possible.
0.1Hz from operating panel input (60Hz base), 0.01Hz from analog
input (60Hz base, 12-bit/0 to 10Vdc), 0.01Hz from computer interface
(60Hz base)
Analog input: ±0.2% of the maximum output frequency (25°C±10°C),
Digital input: ±0.01% (25°C±10°C)
Constant V/f, variable torque, automatic torque boost, True Torque
Control and automatic energy-saving control/maximum voltage
frequency adjustment (25 to 400Hz), torque boost adjustment
(0 to 30%), start-up frequency adjustment (0 to 10Hz).
Adjustable between 0.5 and 10kHz
Insulated gate bipolar (IGBT)
input voltage, or set max. to input voltage sensed at power-up.
Feature not available in H3 drives above 30 HP.
3k ohms potentiometer (1k ohm to 10k ohm-rated potentiometer
can be connected). 0 to 10Vdc (Z
ohm), +/-5 Vdc (Z
=34k ohm), 4 to 20mAdc (Z
in
Proportional gain, integral gain, anti-hunting gain, lag time constant,
and PID error limit adjustments.
0.1 to 6000 secs, accel/decel time 1 or 2 selection, accel/decel
pattern selection
Forward run when F-CC closed (default); reverse run when R-CC
closed (default); reverse run when both closed (default); coast-stop
when ST-CC opened (default); emergency coast stop by a
command from operating panel or terminal block; 3-wire control and
motorized speed pot programmable functions.
Jog run from panel with JOG mode selection. Terminal
block operation possible with parameter settings.
Set frequency plus 15 preset speeds possible with combinations of
CC, SS1, SS2, SS3, and SS4 (default functions).
When a protective function is activated, the system checks main
circuit devices, and attempts to restart. Settable to a maximum
of 10 times; wait time adjustment (0 to 10 secs)
Automatic load reduction during overload (Default setting: OFF).
A coasting motor can be smoothly restarted (Default setting: OFF).
4 groups of 8 patterns each can be set to the 15 preset speed values.
A maximum of 32 different patterns can be run; terminal block
control/repetitive run possible.
Braking starting frequency adjustment (0 to 120Hz), braking current
adjustment (0 to 100%), braking time adjustment (0 to 10secs),
emergency stop braking function, motor shaft stationary control.
Limits the frequency between the set values (0 to max. frequency).
Can be indicated via output contact closure.
3 jump frequency settings (each with unique band settings)
Easy access user group containing all changed parameters
Select to display needed parameter groups and parameters
User's parameter values can be saved into a default library. User
can then default drive to Toshiba's values or to the user's own.
3 - 2
=33k ohm), ±10 Vdc (Z
=67k
in
in
=500 ohm)
in